COMMISSIONING
Run Simulation
To use the run simulation:
1.
Open the Commissioning Menu.
2.
Scroll to Run Simulation and press .
Run Simulation
Ready
Apply Start Signal
3.
Press SSTART or activate the start input. The MVS simulates its pre-start
checks and closes the main contactor relay. The Run LED flashes.
Run Simulation
Pre-Start Checks
SSTORE to Continue
NOTE
If mains voltage is connected, an error message is shown. Remove
mains voltage and proceed to the next step.
Run Simulation
ATTENTION!
Remove Mains Volts
STORE to Continue
4.
Press . The MVS simulates starting. The Run LED flashes.
Run Simulation
Starting X:XXs
STORE to Continue
5.
Press . The MVS simulates running. The Run LED stays on without
flashing and the bypass contactor relay closes.
Run Simulation
Running
Apply Stop Signal
6.
Press SSTOP or activate the stop input. The MVS simulates stopping. The
Run LED flashes and the bypass contactor relay opens.
Run Simulation
Stopping X:XXs
STORE to Continue
7.
Press . The Ready LED flashes and the main contactor relay opens.
Run Simulation
Stopped
STORE to Continue
8.
Press
to return to the commissioning menu.
NOTE
Run simulation can be exited at any stage by pressing the .
.
Protection Simulation
The pprotection simulation simulates activation of each protection mechanism to confirm that the soft starter and
associated control circuits are responding correctly.
To use the protection simulation:
1.
Open the Commissioning Menu.
2.
Scroll to Protection Simulation and press .
3.
Use the
and
buttons to select the protection you want to
simulate.
4.
Press and hold
to simulate the selected protection.
5.
The screen is displayed momentarily. The soft starter's response
depends on the Protection Action setting (parameter group 16).
0.0A
Tripped
Selected Protection
6.
Use
or
to select another simulation, or press
to exit.
NOTE
If the protection trips the soft starter, reset before simulating another protection. If the protection action is
set to 'Warn and Log', no reset is required.