CONFIGURATION
66Q – Local/Remote
Options:
LCL/RMT Anytime (default) LLCL/RMT selection is always enabled.
LCL/RMT When Off
LLCL/RMT selection is enabled when the starter is off.
Local Control Only
The LLCL/RMT button and all remote inputs are disabled.
Remote Control Only
Local control buttons (SSTART, R
RESET, LLCL/RMT) are
disabled.
Description:
Selects when the LLCL/RMT button can be used to switch between local and remote
control, and enables or disables the local control buttons and remote control inputs.
The STOP button on the controller is always enabled.
WARNING
The STOP button on the controller is always enabled. When using two-wire remote control, the soft
starter will restart if the remote start/stop and reset inputs are still active.
6R – Comms in Remote
Options:
Disable Control in RMT
Enable Control in RMT (default)
Description:
Selects whether the starter will accept Start, Stop and Reset commands from the serial
communication network when in Remote mode. The Force Comms Trip and
Local/Remote commands are always enabled.
7 Outputs
The MVS has three programmable outputs, which can be used to signal different operating conditions to associated
equipment.
7A – Relay A Function
Options:
Off
Relay A is not used.
Main Contactor (default)
The relay closes when the MVS receives a start command,
and remains closed as long as the motor is receiving
voltage.
Run
The relay closes when the starter changes to run state.
Trip
The relay closes when the starter trips (refer to parameter
16A to 16X).
Warning
The relay closes when the starter issues a warning (refer
to parameter 16A to 16X).
Low Current Flag
The relay closes when the low current flag activates while
the motor is running (refer to parameter 7M
Low Current
Flag).
High Current Flag
The relay closes when the high current flag activates while
the motor is running (refer to parameter 7N
High Current
Flag).
Motor Temperature Flag
The relay closes when the motor temperature flag
activates (refer to parameter 7O
Motor Temperature
Flag).
Input A Trip
The relay closes when Input A activates to trip the soft
starter.
Input B Trip
The relay closes when Input B activates to trip the soft
starter.
Motor Overload
The relay closes when the starter trips on Motor
Overload.
Current Imbalance
The relay closes when the starter trips on Current
Imbalance.
Undercurrent
The relay closes when the starter trips on Undercurrent.
Instantaneous overcurrent
The relay closes when the starter trips on Instantaneous
Overcurrent.
Frequency
The relay closes when the starter trips on Frequency.
Ground Fault
The relay closes when the starter trips on Ground Fault.
Heatsink Overtemperature
Not applicable to this product.
Phase Loss
The relay closes when the starter trips on Phase Loss.
Motor Thermistor
The relay closes when the starter trips on Motor
Thermistor.
50
MVS Panel User Manual
710-13937-00C