CONFIGURATION
Starter Disable
The MVS can be disabled via the control inputs. An open
circuit across C53, C54 will disable the starter. The MVS
will not respond to start commands. If running, the soft
starter will allow the motor to coast to stop, ignoring the
soft stop mode set in parameter 2H.
D
Description:
Selects the function of Input A.
6B – Input A Name
Options:
Input Trip (default)
Controller
Low Pressure
PLC
High Pressure
Vibration
Pump Fault
Field Trip
Low Level
Interlock Trip
High Level
Motor Temp
No Flow
Motor Prot
Starter Disable
Feeder Prot
Description:
Selects a message for the controller to display when Input A is active.
6C – Input A Trip
Options:
Always Active (default)
A trip can occur at any time when the soft starter is
receiving power.
Operating Only
A trip can occur while the soft starter is running, stopping
or starting.
Run Only
A trip can only occur while the soft starter is running.
Description:
Selects when an input trip can occur.
6D – Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
D
Default:
0 second
Description:
Sets a delay between the input activating and the soft starter tripping.
6E – Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
D
Default:
0 second
Description:
Sets a delay before an input trip can occur. The initial delay is counted from the time a
start signal is received. The state of the input is ignored until the initial delay has
elapsed.
6F, 6G, 6H, 6I, 6J – Input B Trip
Parameters 6F~6J configure the operation of Input B, in the same way as parameters 6A~6E configure
Input A. Refer to Input A for details.
6F
Input B Function
(D
Default: Input Trip (N/O))
6G
Input B Name
(D
Default: Input Trip)
6H
Input B Trip
(Default: Always Active)
6I
Input B Trip Delay (D
Default: 0:00)
6J
Input B Initial Delay (D
Default: 0:00)
6K, 6L – Reserved
These parameters are reserved for future use.
6M – Remote Reset Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the MVS's remote reset input (terminals C41, C42) is normally open or
normally closed.
6N, 6O, 6P – Reserved
These parameters are reserved for future use.
710-13937-00C
MVS Panel User Manual
49