INSTALLATION
6.7
Mounting Instructions - Controller
The controller is secured into place using ten M4 nuts, affixed to the studs on the back of the controller.
112 (4.41)
300 (11.81)
310 (12.20)
340 (13.39)
220 (
8
.6
6)
196 (
7
.7
2)
186 (
7
.3
2)
11073.
A
To mount the controller, make a 186 mm x 300 mm cutout at the desired mounting location. Ensure adequate
clearance (>85 mm) is available behind the mounting location. If you intend to use a communication module, allow
for a minimum clearance of 120 mm behind the mounting panel.
Drill 5 mm holes to accommodate the studs on the controller. Fit the MVS Controller through the cutout and
tighten the nuts onto the studs.
NOTE
Before installation, always ensure that you are using the correct controller for the soft starter. This can be
checked by comparing the serial number on the back of the controller with the serial number on the front
of the power assembly.
1
Serial number
MAIN CONTROL MODULE
MVS-0159-410-V04-C12
S/N: 822805-074
S/N: 822805-074
4.16kV AC, 50/60 Hz
150mm2 at torque 28-30 Nm, 20-22 ft-lb
10 A @ 250 V AC DF 10%, A300, AC-15 6 A @ 250 V AC
#24-#14 AWG, 0.2-2.5 mm2 (0.5 Nm, 4.5 lb-in)
Made in New Zealand
IEC 60047-4-2
IND. CON T. EQ.
32 AN
Z79
1
Z79
MVS 0159-410
3-phase,
S/C withstand:
159A : AC53b 4-20: 1780, 1.16M VA
Type 1 coordination, HRC fuses at prospective 48k
A RMS
Withstand Voltage:
45000 V AC Cat III
Enclosure rating:
IP00, U L Open Type Pollution Degree 3
Aux. terminals:
Aux. contacts:
Power terminals:
Copper or stranded 75
C conductors
03530.
F
710-13937-00C
MVS Panel User Manual
25
Содержание MVSxxxx-V02
Страница 1: ......
Страница 89: ...APPENDIX 88 MVS Panel User Manual 710 13937 00C ...