CONFIGURATION
Parameter 10G
Kickstart Level-2
R
Range:
100% - 700% FLC
D
Default:
500%
Description:
Sets the level of the kickstart current.
Parameter 10H
Stop Mode-2
Options:
Coast To Stop (default)
TVR Soft Stop
Description:
Selects the stop mode.
Parameter 10I
Stop Time-2
Range:
0:00 - 4:00 (minutes:seconds)
D
Default:
0 second
Description:
Sets the stop time.
11 RTD/PT100 (Reserved)
This parameter group is reserved for future use.
12 Slip-Ring Motors
These parameters allow the soft starter to be configured for use with a slip-ring motor.
12A – Motor 1 Ramp
Options:
Single Ramp (default)
Dual Ramp
Description:
Selects whether to use a single or dual current ramp profile for soft starting. Set to
single ramp for non-slip ring induction motors, or dual ramp for slip-ring induction
motors.
12B – Motor 2 Ramp
Options:
Single Ramp (default)
Dual Ramp
Description:
Selects whether to use a single or dual current ramp profile for soft starting. Set to
single ramp for non-slip ring induction motors, or dual ramp for slip-ring induction
motors.
Parameter 12B selects the ramp configuration for the secondary motor.
12C – Changeover Time
Range:
100 - 500 (milliseconds)
D
Default:
150 milliseconds
Description:
Sets the delay between the rotor resistance relay closing and the low resistance current
ramp starting. Set so that the contactor has enough time to close, but the motor does
not slow down.
Parameter 12C only applies if parameter 12A or 12B is set to 'Dual Ramp', and an
output relay is set to 'Changeover Contactor'.
12D – Slip-Ring Retard
Range:
10% - 90%
D
Default:
50%
Description:
Sets the level of conduction after the rotor resistance contactor closes, as a percentage
of full conduction.
Set so that no current pulse occurs, but the motor retains enough speed to start
correctly.
15 Advanced
15A – Access Code
Range:
0000 - 9999
D
Default:
0000
Description:
Sets the access code to control access to restricted sections of the menus.
Use the
and
buttons to select which digit to alter and use the
and
buttons to change the value. After the last digit is set press STORE.
NOTE
In the event of a lost access code, contact your supplier for master access code that allows you
to re-program a new access code.