CONFIGURATION
88E, 8F, 8G, 8H – User-Programmable Screen
Options:
Blank
Displays no data in the selected area, allowing long
messages to be shown without overlapping.
Starter State
The starter's operating state (starting, running, stopping or
tripped). Only available for top left and bottom left
positions on the screen.
Motor Current
The average current measured on three phases.
Motor pf
The motor's power factor, measured by the soft starter.
Mains Frequency
The average frequency measured on three phases.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the thermal
model.
kWh
The number of kilowatt hours the motor has run via the
soft starter.
Hours Run
The number of hours the motor has run via the soft
starter.
Analog Input
n/a
Mains Voltage
The average voltage measured on three phases.
Description:
Selects which information will be displayed on the programmable monitoring screen.
8E
User Screen - Top Left
Default: Starter State
8F
User Screen - Top Right
Default: Blank
8G
User Screen - Bottom Left
Default: kWh
8H
User Screen - Bottom Right Default: Hours Run
8I, 8J, 8K, 8L – Performance Graphs
The MVS has a real-time performance graph to report the behaviour of critical operating parameters.
Parameter 8I
Graph Data
Options:
Current (% FLC) (default)
Current as a percentage of motor full load current.
Motor Temp (%)
Motor temperature as a percentage of the motor rated
current (calculated by the soft starter's thermal model).
Motor kW (%)
Motor kilowatts. 100% is motor FLC (parameter 1A)
multiplied by mains voltage. Power factor is assumed to
be 1.0.
3 . V . I
FLC
. pf
1000
Motor kVA (%)
Motor kilovolt amperes. 100% is motor FLC (parameter
1A) multiplied by mains voltage.
3 . V . I
FLC
1000
Motor pf
Motor power factor, measured by the soft starter.
Voltage (%Mains)
The average voltage measured on three phases as a
percentage of the mains voltage.
Description:
Selects which information the graph will display.
Parameter 8J
Graph Timebase
Options:
10 seconds (default)
10 minutes
30 seconds
30 minutes
1 minute
1 hour
5 minutes
Description:
Sets the graph time scale. The graph will progressively replace the old data with new
data.
Parameter 8K
Graph Maximum Adjustment
Range:
0% – 600%
D
Default:
400%
Description:
Adjusts the upper limit of the performance graph.
Parameter 8L
Graph Minimum Adjustment
Range:
0% – 600%
D
Default:
0%
Description:
Adjusts the lower limit of the performance graph.
710-13937-00C
MVS Panel User Manual
53