CONFIGURATION
77P, 7Q, 7R, 7S – Analog Output A
The MVS has an analog output, which can be connected to associated equipment to monitor motor
performance.
Parameter 7P
Analog Output A
Options:
Current (% FLC) (default)
Current as a percentage of motor full load current.
Motor Temp (%)
Motor temperature as a percentage of the motor rated
current (calculated by the soft starter's thermal model).
Motor kW (%)
Motor kilowatts. 100% is motor FLC (parameter 1A)
multiplied by mains voltage. Power factor is assumed to
be 1.0.
3 . V . I
FLC
. pf
1000
Motor kVA (%)
Motor kilovolt amperes. 100% is motor FLC (parameter
1A) multiplied by mains voltage.
3 . V . I
FLC
1000
Motor pf
Motor power factor, measured by the soft starter.
Voltage (%Mains)
The average voltage measured on three phases as a
percentage of the mains voltage.
Description:
Selects which information will be reported via Analog Output A.
Parameter 7Q
Analog A Scale
Range:
0-20 mA
4-20 mA (default)
Description:
Selects the range of the analog output.
Parameter 7R
Analog A Maximum Adjustment
Range:
0% - 600%
D
Default:
100%
Description:
Calibrates the upper limit of the analog output to match the signal measured on an
external current measuring device.
Parameter 7S
Analog A Minimum Adjustment
Range:
0% - 600%
D
Default:
0%
Description:
Calibrates the lower limit of the analog output to match the signal measured on an
external current measuring device.
7T~7W – Reserved
These parameters are reserved for future use.
8 Display
These parameters allow the controller to be tailored to individual users' requirements.
8A – Language
Options:
English (default)
Português
Chinese
Français
Español
Italiano
Deutsch
Russian
Description:
Selects which language the controller will use to display messages and feedback.
8B, 8C – F1 and F2 Button Action
Options:
None
Setup Auto-Start/Stop
Description:
Selects the function of the FF1 and FF2 buttons on the controller.
8B
F1 Button Action
Default: Setup Auto-Start/Stop
8C
F2 Button Action
Default: None
8D – Display A or kW
Options:
Current (default)
Motor kW
Description:
Selects whether the MVS will display current (amperes) or motor kilowatts on the main
monitoring screen.
52
MVS Panel User Manual
710-13937-00C
Содержание MVSxxxx-V02
Страница 1: ......
Страница 89: ...APPENDIX 88 MVS Panel User Manual 710 13937 00C ...