INSTALLATION
6.8
Power Terminations
Models V02 ~ V07
T3B, T3, L3
T2B, T2, L2
L1
T1B
T1
6
(0.24)
25
(0.98)
13
(0.51)
Use only M10 high tensile grade 8.8 threaded fasteners for all terminations. Use a pre-load torque setting between
28 ~ 30 Nm. Use only Belleville washers.
Side view
Top view
03217.D
A
B
C D
1
0
131.
B
J
J
E
F
G
H
I
H
I
T1
T2
T3
L3
L2
L1
T3B
T2B
T1B
A
B
A
B
C
D
E
F
G
H
I
J
mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) mm (inch) mm (inch)
MVSxxxxV02*
228
(8.98)
79
(3.11)
744
(29.29)
760
(29.92)
79
(3.11)
129
(5.08)
179
(7.05)
200
(7.87)
200
(7.87)
200
(7.87)
MVSxxxxV03*
MVSxxxxV04*
MVSxxxxV06
228
(8.98)
79
(3.11)
792
(31.18)
806
(31.73)
107
(4.19)
164
(6.46)
222
(8.72)
268
(10.55)
268
(10.55)
268
(10.55)
MVSxxxxV07
NOTE
For models MVSxxxxV02 to MVSxxxxV04, these dimensions apply up to 321 A. For the same models with
current ratings of 500 A, the MVSxxxxV06 dimensions apply.
26
MVS Panel User Manual
710-13937-00C