INSTALLATION
Site installation of panels should only be carried out by specially trained and skilled personnel. The location must be
adequately prepared with wall openings, ventilation ducts and cabling connections to the power supply.
6.1
Clearance Requirements
While installing AuCom switchgear panels, ensure that minimum clearance requirements are met.
600
1200
600
2800
14
091.
A
2322
600
Plan view
Side view
NOTE
Standard panels may be mounted closer to the wall from the rear if required. Consult AuCom if closer
wall mounting is required.
6
Installation
710-13937-00C
MVS Panel User Manual
17