- 61 -
6.3
Solving Qc1111™/Qc2111™
controller alarms
6.3.1
Qc1111™/Qc2111™ alarms and
remedies
If an alarm condition occurs, an icon is displayed in
the Alarm icon section of the LCD to indicate the
alarm that is current active on the controller.
In the event of a
warning alarm
, the LCD only
displays the Alarm Icon.
In the event of an
electrical trip or shutdown alarm
,
the module displays the Alarm icon and the STOP/
RESET button LED begins to flash.
If multiple alarms are active at the same time, the
Alarm icon automatically cycles through all the
appropriate icons to indicate each alarm which is
active.
Example:
If the Qc1111™/Qc2111™ controller detected a
charge alternator failure alarm, a delay over current
alarm and an AC under voltage alarm at the same
time, it would cycle through all of the icons, as shown
below: