- 25 -
4
Operating instructions
4.1
Before starting
– With the generator set standing level, check the
engine oil level and top up if necessary. The oil
level must be near to, but not exceed the high mark
on the engine oil level dipstick.
– Check the coolant level in the expansion tank of
the engine cooling system. The coolant level must
be near to the FULL mark. Add coolant if
necessary.
– Drain any water and sediment from the fuel pre-
filter. Check the fuel level and top up if necessary.
It is recommended to fill the tank after the day’s
operation to prevent water vapor in a nearly empty
tank from condensing.
– Drain leaking fluid from the frame.
– Check the vacuum indicator of the air filter. If the
red part shows completely, replace the filter
element.
– Press the dust evacuator of the air filter to remove
dust.
– Check the generator set for leakage, tightness of
wire terminals, etc. Correct if necessary.
– Check that circuit breaker Q600 is switched off.
– Check that no circuit breakers have tripped and
that the emergency stop is in the OUT position.
– Check that the load is switched off.
– Check that the earth fault protection (FS1) has not
tripped (reset if necessary).
4.2
Operating and setting
Qc1111™/Qc2111™
4.2.1
Setting the Qc1111™/Qc2111™
4.2.1.1
Button overview
In your own interest, always strictly
observe all relevant safety
instructions.
Do not operate the generator set in
excess of the limitations mentioned
in the Technical Specifications.
Local rules concerning the setting
up of low voltage power installations
(below 1000 V) must be respected
when connecting site distribution
panels, switch gear or loads to the
generator set.
At each start-up and at any time a
new load is connected, the earthing
and protections (GB trip and earth
leakage relay) of the generator set
must be verified. Earthing must be
done either by the earthing rod or, if
available, by an existing, suitable
earthing installation. The protective
system against excessive contact
voltage is not effective unless a
suitable earthing is made.
!
1
STOP/RESET:
Allows to put the
control module in
Stop/Reset
mode.
When pressing the STOP button, the
generator set will unload, the fuel
supply de-energises and the engine
shuts down.
Pressing the STOP button will also
clear any alarm conditions for which
the triggering criteria have been
removed.
2
AUTO:
Allows to put the control
module in
Auto
mode.
Qc2111
1
2
3
4
5