- 66 -
6.3.2.3
Shutdown alarm icons
Shutdown alarms are latching and immediately stop the generator set. On initiation of the shutdown condition the module de-energises all the ‘Delayed Load Output’ and
the ‘Close Gen Output’ outputs to remove the load from the generator set. Once this has occurred, the module shuts the generator set down immediately to prevent further
damage. The alarm must be accepted and cleared, and the fault removed to reset the module.
Shutdowns are latching alarms and to remove the fault, press the STOP/RESET button on theQc1111™ /Qc2111™ module.
The alarm condition must be rectified before a reset will take place. If the alarm condition remains, it is not possible to reset the unit.
!
Display
Description
Reason
Auxiliary Inputs
The module detects that an auxiliary input which has been user configured to create a fault
condition has become active.
Analogue Input Configured As Digital
The analogue inputs can be configured to digital inputs. The module detects that an input
configured to create a fault condition has become active.
Fail To Start
The engine has failed to start after the configured number of start attempts.
Low Oil Pressure
The module detects that the engine oil pressure has fallen below the low oil pressure pre-alarm
setting level after the Safety On timer has expired.
Engine High Temperature
The module detects that the engine coolant temperature has exceeded the high engine
temperature pre-alarm setting level after the Safety On timer has expired.
Under Speed
The engine speed has fallen below the under speed pre-alarm setting.
Over Speed
The engine speed has risen above the over speed pre-alarm setting.