- 73 -
9.3.5
Outlet sockets (S) - 3-phase
A brief description of all outlet sockets and circuit
breakers provided on the generator set is given
hereafter:
XS1..... 1-phase outlet socket (230/277 V AC)
Provides phase L1, neutral and earthing.
XS2..... 1-phase outlet socket (230/277 V AC)
Provides phase L2, neutral and earthing.
XS3..... 3-phase outlet socket (400/480 V AC)
Provides phases L1, L2 and L3, neutral and
earthing.
XS4..... 3-phase outlet socket (400/480 V AC)
Provides phases L1, L2 and L3, neutral and
earthing.
XS5..... 3-phase outlet socket (400/480V AC)
Provides phases L1, L2 and L3, neutral and
earthing.
Q601 ... Circuit breaker for XS1
Interrupts the power supply to XS1 when a
short-circuit occurs at the load side, or when
the overcurrent protection (16 A) is
activated. When tripped, Q601 interrupts
phase L1 towards XS1. It can be reset after
eliminating the problem.
Q602 ... Circuit breaker for XS2
Interrupts the power supply to XS2 when a
short-circuit occurs at the load side, or when
the overcurrent protection (16 A) is
activated. When tripped, Q602 interrupts
phase L2 towards XS2. It can be reset after
eliminating the problem.
Q603 ... Circuit breaker for XS3
Interrupts the power supply to XS3 when a
short-circuit occurs at the load side, or when
the overcurrent protection (16 A) is
activated. When tripped, Q603 interrupts the
three phases towards XS3. It can be reset
after eliminating the problem.
Q604 ... Circuit breaker for XS4
Interrupts the power supply to XS4 when a
short-circuit occurs at the load side, or when
the overcurrent protection (32 A) is
activated. When tripped, Q604 interrupts the
three phases towards XS4. It can be reset
after eliminating the problem.
Q605 ... Circuit breaker for XS5
Interrupts the power supply to XS5 when a
short-circuit occurs at the load side, or when
the overcurrent protection (63 A) is
activated. When tripped, Q605 interrupts the
three phases towards XS5. It can be reset
after eliminating the problem.
Circuit breaker Q600 does not only
interrupt the power supply towards
X10, but also towards XS1, XS2,
XS3, XS4 and XS35.
Make sure to switch on circuit
breakers Q600, Q601, Q602, Q603,
Q604 and Q605 after starting the
generator set when power is supplied
by means of XS1, XS2, XS3, XS4 or
XS5.
Stop
Auto
Start
S1
XS3
XS4
XS5
XS2
XS1
Q600
Q601-605
!