- 36 -
Engine running
Once the engine is running and all starting timers
have expired, the animated Engine Running icon is
displayed.
In manual mode, the load is not transferred to the
generator set unless a ‘loading request’ is made. A
loading request can come from a number of sources.
– Activation of an auxiliary input that has been
configured to Remote Start On Load or Auxiliary
Mains Fail.
– Activation of the inbuilt exercise scheduler if
configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive
until the Oil Pressure has risen. This prevents
excessive wear on the engine.
Once the generator set has been placed on load, it is
not automatically removed. To manually remove the
load, either:
– Press the AUTO button to go to Auto mode.
The set observes all Auto mode start requests and
stopping timers before beginning the Auto mode
Stopping Sequence.
– Press the STOP/RESET button to remove load
and stop the generator set.
– Activation of an auxiliary input that has been
configured to Generator Load Inhibit.
Stopping
In manual/start mode the set will continue to run until
either:
– The STOP/RESET button is pressed
The delayed load outputs are de-activated
immediately and the set immediately stops.
– The AUTO button is pressed.
The set observes all Auto mode start requests and
stopping timers before beginning the Auto mode
Stopping Sequence.
4.2.3
Front panel configuration
This configuration mode allows the operator limited
customising of the way the module operates.
Use the module’s navigation buttons to traverse the
menu and make value changes to the parameters.
1. Press the STOP and AUTO buttons together to
enter the editor mode.
2. Press the UP or DOWN button to cycle through
the front panel editor to select the required page in
the configuration tables.
3. Press the START button to select the next
parameter or the STOP button to select the
previous parameter within the current page.
1
Next Section (101-201-301)
2
Previous Section (301-201-101)
3
Previous Parameter (103-102-101)
4
Edit or Save Parameter
5
Next Parameter (101-102-103)
Qc2111
1
2
3
4
5