MAGB2 User Guide
32
V1.7 2021-10-01
9=On < F1,
10=Volume
Pulse
2030
2029
Bool
0
0
1
0
Load Default
Settings
R/W
2032
2031
Longint
0
0
9999
1111
Password Setup R/W
2034
2033
Longint
0
1
247
1
Modbus Slave
Address
R/W
2036
2035
Longint
0
0
5
2
Modbus
BaudRate,
0=4800,
1=9600,
2=19200,
3=38400
4=57600
5=115200
2038
2037
Longint
0
0
3
3
Modbus Parity,
0=Even, 1
stopbit,
1=Odd, 1
stopbit,
2=None, 2
stopbits,
3=None, 1
stopbit
R/W
2040
2039
Bool
0
0
1
0
Totalizer cycling
0= OFF,
1= ON
R/W
2042
2041
Longint
0
0
5
0
Module select*
0=OFF,
1=RS485,
2=GPRS,
3=IOUT,
4=LoRa,
5=MBUS
R/W
*Will be transferred to automatic function later
Datalogger Interval
– this function selects how often data is written to the datalogger.
Air Detector
–
this option allows selecting empty pipe check. Default ON. If the Air detector is active and
the pipe is empty, the unit automatically turns down the excitation to prolong battery life.
Delete Aux + Volume
–
write value different to zero for erasing the auxiliary flow totalizer.
Samples per Avg.
– the number of samples that the flowmeter will use for calculation of its displayed
average flow value. Default 3.
Frequency Output Setting - Signal
– see chapter Frequency output
Frequency Output
– Q1kHz
– see chapter Frequency output
Relay
– Comparator Flow 1
- see chapter Pulse Output.
Relay
– Comparator Flow 2
- see chapter Pulse Output.
Relay
– Comparator Hysteresis 1
- see chapter Pulse Output.
Relay
– Comparator Hysteresis 2
- see chapter Pulse Output.
Relay
– Volume per Pulse
- see chapter Pulse Output.
Relay
– Pulse Width
- see chapter Pulse Output.
Relay
– Pulse Output – setting signal
- see Pulse Output.
Load default settings
–
Load default factory setting or users changing setting on function Save setting.