MAGB2 User Guide
27
V1.7 2021-10-01
11.5. Real-time measurement - Integer
Modbus
register
Modbus
address
Data type
No. of
decimal
Min
Value
Max Value
Description
Read/
Write
100
99
Longint
3
-10^7
10^7
FLOW
R
102
101
Longint
0
0
2^32
TOTAL DIG
R
104
103
Longint
6
0
2^32
TOTAL DEC
R
106
105
Longint
0
0
2^32
AUX+ DIG
R
108
107
Longint
6
0
2^32
AUX+ DEC
R
110
109
Longint
0
0
2^32
TOTAL+ DIG
R
112
111
Longint
6
0
2^32
TOTAL+ DEC
R
114
113
Longint
0
0
2^32
TOTAL- DIG
R
116
115
Longint
6
0
2^32
TOTAL- DEC
R
118
117
Bool
0
0
1
Reserved
R
120
119
Longint
0
0
2^16
ERROR CODE
R
122
121
Longint
0
0
2^32
Ext. Temperature
R
124
123
Longint
0
0
2^32
Ext. Pressure
R
FLOW
Unit: m3/h - it is not possible to change it.
Real value = Actual value / 1000.
TOTAL (TOTAL +, TOTAL -, AUX +) DEC and DIG
Unit: m
3
– it is not possible to change it.
The final number is given by the sum of the whole and the decimal. Example: Resulting Total measurement
= (TOTAL DIG) + (TOTAL DEC*10^-3).
ERROR CODE
Convert read value to binary number. Number one means error. For more information see chapter 19.
Ext. Temperature
If external measurements module temperature is used then real temperature value = Actual value divided
by 10.
Ext. Pressure
If external measurements module pressure is used then real pressure value = Actual value divided by
1000.