94
RS-232C Command Set
bold font. Please read the comments below each command as some commands include one or more commas
and in other cases a comma will separate multiple commands.
The following symbols and syntax are used:
C
= Shorthand for carriage-return, line-feed
U = UTC Time
L = Local Time
soh = An ASCII character (start of header) = Hex 01
bel = An ASCII character = Hex 07
n = integer used for various numerical values
yyyy = four digit year
ddd = Julian day-of-year
mm = month
hh = hour
mm = minute
ss = second
www = Day of Week
= Underlines are used for clarity only and graphically represent the location of
ASCII spaces.
11.2.1
Installing Custom Broadcast Strings
The Model 1201B/C allows the user to construct and install two custom strings to be broadcast from COM1
and COM2: Custom string A from COM 1 and Custom String B from COM 2. If the standard strings
are not exactly what you require, you may want to construct one that better matches your requirements.
For information on constructing, installing and using a custom broadcast string, please see Section 11.4.
Section 11.4 also includes a small tutorial on constructing strings using some of the common strings already
available in Section 11.2.2 below.
11.2.2
Broadcast Mode Commands
Broadcast Mode: INTERROGATE (Broadcast OFF)
Command:
B0, O0
B0 deactivates the RS-232C broadcast mode (resets to interrogate mode) on COM1. O0 deactivates the
RS-232C broadcast mode on COM2.
Response:
C
Broadcast Mode: ASCII STD
Command:
B1, O1
B1 configures the clock to broadcast the time-of-day as ASCII standard data from COM1. O1 configures
the clock to broadcast ASCII standard data from COM2.
Response:
<
soh
>
ddd:hh:mm:ss
C
Broadcast Mode: VORNE STD
Command:
B2, O2
B2 configures the clock to broadcast data formatted for Vorne large format time displays from COM1. O2
configures the clock to broadcast Vorne-formatted data from COM2. Refer to Arbiter Systems Application
Note 103 for more information on using large format displays with GNSS clocks from Arbiter Systems.
Содержание 1201B
Страница 4: ...iv ...
Страница 153: ...B 7 Four Fiber Optic Outputs 135 Figure B 4 Jumper Locations ...
Страница 155: ...B 8 8 Channel High Drive IRIG B Amplifier 137 Figure B 5 8 High Drive Outputs Jumper Locations ...
Страница 171: ...B 10 Four Additional Outputs and Dry Contacts 25 50 Vdc 153 Figure B 7 Option Connector Signal Locations ...
Страница 222: ...Appendix E Statement of Compliance The following page is a statement of compliance that includes Model 1201B and 1201C ...