Tempering Valve:
The tempering valve for the Aqua-Hot mixes the heated do-
mestic water from the boiler tank with cold domestic water at
a preset ratio to reduce the risk of scalding.
Troubleshoot the tempering valve if the following condition
has occurred:
There is a lack of hot domestic water.
Troubleshooting:
1. Inspect the tempering valve to ensure that it is not
leaking.
2.
Test the temperature of the hot water using a digital
thermometer at one of the hot water faucets. Water
Temperature should range between 115° F - 123° F. If
the proper range cannot be set follow the instructions in
this section to replace the tempering valve.
3.
Test the tempering valve’s functionality by turning the
knob.
If the tempering valve’s knob does not turn freely, fol-
low the instructions in this section to replace the temper-
ing valve’s internal components
Replacement Procedure:
F
AILURE
TO
DISCONNECT
ALL
POWER
SUPPLIES
AND
/
OR
TO
ALLOW
THE
HEATER
TO
COOL
BEFORE
SERVICING
COULD
CAUSE
SERIOUS
DAMAGE
OR
PERSONAL
INJURY
.
1.
Turn the motor home’s water pump off.
2.
Drain the water pressure by opening the faucets and al-
lowing the water to drain.
3.
Follow the instructions for removing the diesel burner..
4.
Using Channel Lock Pliers, remove the Thermostat and
Bonnet Assembly.
5. Once the thermostat and bonnet assembly has been re
moved, replace the o-ring, stainless steel spring, and
thermostat.
6.
Re-Install the bonnet assembly, and tighten with channel
lock pliers.
7.
Turn the motor home’s water pump back on and check
for leaks.
8. Follow the instructions for re-installing the diesel burn-
er.
9. Turn the diesel burner on and let the heater come up to
full operating temperature.
10. Test heater for proper operation. Verify that the
replacement tempering valve has been set to the proper
setting by taking a digital thermometer to a hot water
faucet and set the water temperature between
115ºF - 123ºF .
NOTE:
Prior to trouble shooting the tempering valve, it is
recommended to review the Lack of Hot Water Trouble-
Shooting guide in section 9.
NOTE:
If the Hot line coming out of the Aqua Hot into the
tempering valve is hot, but the mix side of the tempering
valve is luke warm/cold, The tempering valve may be
faulty.
FAILURE TO PROPERLY SET THE HOT WATER
TEMPERATURE BETWEEN 115ºF - 123ºF COULD
RESULT IN SEVERE BURNS.
Содержание AHE-100-02S
Страница 1: ...SERVICE MANUAL 2011 Aqua Hot Heating Systems Inc AHE 100 02S ...
Страница 2: ... Page 2 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 76: ... Page 76 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 77: ... Page 77 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 104: ... Page 104 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 105: ... Page 105 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...