Pumps
Circulation Pumps A, B, and C:
The Zone circulation pump first draw the heated antifreeze
and water heating solution from the Aqua-Hot’s boiler tank,
then propel it through the hydronic heating system’s interior
heat plumbing.
Troubleshoot the Zone circulation pumps if the following
condition has occurred:
The Zone circulation pump is not operating.
There is a lack of heat in the coach.
Troubleshooting:
1. Turn on the interior room thermostat corresponding to the
Zone pump not operating.
A. Using a Volt Meter , Check for voltage on the Fuse
Block for the zone pumps, Fuse C.
a. If No voltage, replace the fuse.
b. If Yes continue.
B. Using a Volt Meter, Check and ensure that the cor-
responding zone relay is sending voltage to the
pump at pin 6.
a. If No voltage is present troubleshoot the
zone relay.
b. If Yes continue.
C. Check the Zone pump for voltage.
a. If there is voltage and the zone pump is not
operating, follow the zone pump
replacement procedure in this book.
Replacement Procedure:
F
AILURE
TO
DISCONNECT
ALL
POWER
SUPPLIES
AND
/
OR
TO
ALLOW
THE
HEATER
TO
COOL
BEFORE
SERVICING
COULD
CAUSE
SERIOUS
DAMAGE
OR
PERSONAL
INJURY
.
1.
Ensure that the Aqua-Hot has been completely shut
down and that all power sources have been disconnect-
ed. Also, because this replacement procedure will in-
volve the potential for hot coolant, be sure the heater is
adequately cooled.
2.
Shut off both the return and the supply ball valves com-
ing out of the aqua hot boiler tank..
3.
Disconnect the interior heating zone line from the check
valve.
4.
Unscrew the check valve from the Aqua-Hot zone
circulation pump.
5.
Disconnect the defective circulation pump’s wires by
removing the protective loom, and cutting both the posi-
tive and negative wires with wire cutters.
6.
Using a 3/4” and a 1 1/8” wrench disconnect the union
securing the zone circulation pump in place.
7.
Remove the zone circulation pump.
8.
Using a 1” wrench remove the copper pump stand from
the defective pump.
9. Wrap the threads of the new replacement pump with a
thread seal tape.
10
. Install the copper pump stand onto the replacement zone
circulation pump, and tighten down with a 1” wrench.
NOTE:
Reference wiring Schematic in Appendix A.
NOTE:
The zone pump can be tested by connecting it to
an external 12 Volt-DC power source to verify that the pump
is defective.
NOTE:
When the interior heating zone line is disconnected
from the check valve, approximately 2 quarts of antifreeze
will leak out of the interior heating zone line.
NOTE:
Be sure to install the copper pump stand onto the
inlet side of the zone circulation pump. Reference Fig. 15
NOTE:
Once the check valve is removed there is pump nut,
securing the pump in place that will also need to be
removed.
NOTE:
Before Replacing the Pump remove and inspect the
brushes on the pump. If they are less than 1/8” the brushes
are to worn and will prevent the pump from operating.
Содержание AHE-100-02S
Страница 1: ...SERVICE MANUAL 2011 Aqua Hot Heating Systems Inc AHE 100 02S ...
Страница 2: ... Page 2 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 76: ... Page 76 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 77: ... Page 77 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 104: ... Page 104 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 105: ... Page 105 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...