— Page 85 —
© 2011 Aqua-Hot
®
AHE-100-02S Hydronic Heating System Service Manual—Rev. B
A
PPENDIX
C: F
UEL
P
RESSURE
C
HECK
AND
A
DJUSTMENT
Instructions for Adjusting Fuel Pressure
Step 1: Follow the directions for Checking the Fuel Pressure in this section.
1. Remove the Diesel Burner and install the Fuel Pressure Gauge .
WARNING!
A spark will appear across the ignition electrodes for a brief moment after the diesel burner has been activated.
DO NOT attempt to make any fuel pressure adjustments until the spark has disappeared. Failure to do so may
result in serious bodily injury. In some installations it may be necessary to shine a light on the flame sensor to
simulate a flame condition to shot of the ignition coil.
2. Turn the diesel burner switch to the on position. A pressure will register on the fuel pressure gauge
once the fuel solenoid opens (after approx. 10-20 seconds.)
Figure C5
Figure C6