— Page 25 —
© 2011 Aqua-Hot
®
AHE-100-02S Hydronic Heating System Service Manual—Rev. B
S
ECTION
5: A
QUA
-H
OT
C
OMPONENTS
11.
Install the replacement pump onto the Aqua Hot, and t
tighten down the union previously loosened.
12.
Re-Install the check valve onto the Aqua-Hot zone cir-
culation pump. The arrow on the check valve must
point away from the circulation pump.
13
. Reconnect the interior heating zone fitting and line to
the check valve.
14.
Reconnect the wires on the replacement pump to the
wire harness on the heater by using a red butt connector.
Be sure to review the wiring schematic in appendix A
for proper pump wiring.
15.
Refill the Aqua-Hot boiler tank with the antifreeze and
water heating solution.
NOTE: The Aqua Hot zone circulation pump is not a self
priming pump. If the circulation pump gets an air pocket, it
will be necessary to bleed the air out of the zone circulation
pump. Reference appendix B For the proper zone circula-
tion pump bleeding procedure.
C
B
A
Copper
Pump Stand
Union
Check Valve
Back view of
pump
Figure 15
Содержание AHE-100-02S
Страница 1: ...SERVICE MANUAL 2011 Aqua Hot Heating Systems Inc AHE 100 02S ...
Страница 2: ... Page 2 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 76: ... Page 76 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 77: ... Page 77 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 104: ... Page 104 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 105: ... Page 105 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...