— Page 29 —
© 2011 Aqua-Hot
®
AHE-100-02S Hydronic Heating System Service Manual—Rev. B
Zone Relay: Interior Heat Exchanger Fans/
Zone Pumps
The Zone relay is an electrical device where the DC circuit
from the Interior Room Thermostat determines whether the
DC power is permitted to flow to the circulation pump and
the heat exchanger fans. This allows the Interior Room
Thermostat to switch both the fans and circulation pump on.
Troubleshoot the Zone relay if either of the following condi-
tions have occurred:
The Interior fans fail to operate.
The circulation pump fails to operate
Troubleshooting:
If the
Interior heat exchanger Fans
fail to operate:
1. Turn the corresponding room thermostat on, on the inte-
rior of the motor home, ensuring the thermostat is set at
the maximum heat setting, to ensure they will call for
heat.
2. Using a Digital Volt meter, verify that the room
thermostat has sent a ground signal to the terminal strip
for the corresponding zone.
If there is no ground signal from the interior room
thermostat inspect the wire going to the room
thermostat. If the wire is good, replace the interior room
S
ECTION
5: A
QUA
-H
OT
C
OMPONENTS
3. Locate the Fuse block, and using a volt meter, check for
12VDC on the C (Pumps) & D (Fans) Fuse.
If no power is present check the fuse.
4. On the Right-Hand side of the Zone relay check pins A, 7,
and 9 for 12 VDC +
If no power is present: Inspect the wires and verify
the C and D fuses are good.
5. On the Zone Relay check pin B for ground.
If there is not a ground present, verify that the room
thermostat is calling for heat, and that it is sending a
ground signal to the relay.
6. On the Left Hand Side of the zone relay, check pin 4
(Fans) or pin 6 (pumps) for 12 VDC +.
If no power is present replace the Zone Relay.
Replacement Procedure:
1. Release the clip securing the relay in place.
2. Pull the relay out of the relay socket.
3. Install the replacement relay into the relay socket.
4. Secure the relay in place with the relay clip.
Figure 18
NOTE:
If there is no ground for pin 0, it is possible to by-
pass the motor homes’ interior room thermostat by supply-
ing an external ground to the terminal block for the particu-
lar zone being trouble shot. If the zone works with the inte-
rior room thermostat bypassed the problem is located in the
motor home, not within the heating system.
NOTE:
If the new zone relay does not fix the problem, it is
possible the relay socket has gone bad. The relay socket can
be removed by pulling on the release tab on the right hand
side of the relay socket
Содержание AHE-100-02S
Страница 1: ...SERVICE MANUAL 2011 Aqua Hot Heating Systems Inc AHE 100 02S ...
Страница 2: ... Page 2 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 76: ... Page 76 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 77: ... Page 77 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B APPENDIX A WIRING DIAGRAM ...
Страница 104: ... Page 104 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...
Страница 105: ... Page 105 2011 Aqua Hot AHE 100 02S Hydronic Heating System Service Manual Rev B ...