AQUAKOND AKY
CONDENSING BOILER
23
code HC0048.10GB ed.B-1811
AKY
The switches program the address by using a binary code; the corresponding values
are listed below: 1°=1; 2°=2; 3°=4; 4°=8; 5°=16; 6°=32.
Therefore, to program address 13, you must set to ON switches 4°+3°+1°; the
matching address will be 8+4+1=13.
When an address is changed, the PCB must be powered off and on again.
External probe(s) - optional
(code G07202)
7÷
25 Vdc
0 V
MOD-BUS connection
Power supply connection
ID2 digital input
A
DETTAGLIO A
A
DETTAGLIO A
A
DETTAGLIO A
CPU-SMART
#1
CPU-SMART
#2
CPU-SMART
#n
Setting switch
Heater address
+12V GND D+ D-
+12V GND D+ D-
+12V GND D+ D-
ID2-IDC2 contacts jumper
M1
M2
SmartEASY/WEB
4
3
2
1
+VIN GND
A+
B-
Remote ON/OFF contact
10
9
8
7
6
5
4
3
2
1
ID1
GND
ID2
GND
NT
C1
AGND
AN3/
NTC3
AGND
NT
C2
AGND
5.5.3. Connecting SmartEASY/WEB remote control
The SmartEASY/WEB must be connected by using the connector
provided. Connect the power supply, making sure polarity is
correct.
Connect the Modbus RS485 network to its terminals, making
sure polarity is correct.
In case of several boilers, the remote control must be electrically
connected to a single boiler and the D+ and D- terminals must
be connected making sure polarity is correct; the network can
be made both as a serial and star network.
N
ote: For multiple boiler cascading management in a single
zone, connect a single SmartEASY/WEB remote control.
Use shielded cable having a section equal to or greater than
0.4 sq.mm.
T
he correct address for each PCB must then be set up.
Addresses must start from 1 to N without interruptions in the
numbering sequence. The address of each PCB, if different from
zero, is displayed on the LCD as Axx, where xx is the address.
To program the SmartEASY/WEB, please read the operating
manual supplied with the accessory.