AQUAKOND AKY
CONDENSING BOILER
29
code HC0048.10GB ed.B-1811
AKY
6.
SERVICING INSTRUCTIONS
The first start-up must be carried out only by authorised service centres.
The first start-up also includes a combustion analysis, which is compulsory.
The equipment is certified in the EC and non-EC countries, according to the gas categories shown below.
6.1. Country Table - Gas Category
NOTE: Starting from 01/01/18 in the Netherlands only equipment certified with the new ‘cat. K’ gas may be installed.
In the Netherlands, AKY units can be installed only with LPG (G30/G31) since they are not cat. K certified.
The following information is clearly printed on the equipment packaging: country of destination, gas category and equipment code,
all translated into the language of the destination country.
The code allows finding out the factory settings:
Codes with no extension:
•
AKY070IT
if there is no extension, it means that the equipment has been tested and set to run with natural gas
[G20]
Codes with extension:
the fourth letter indicates the type of gas the equipment has been set up for:
•
AKY070FR-xxx
0
0 indicates that the equipment has been tested and set up for natural gas [G20]
•
AKY070MT-xxx
1
1 indicates that the equipment has been tested and set up for LPG [G31]
•
AKY070DE-xxx
2
2 indicates that the equipment has been tested and set up for 'LL' natural gas [G25]
Another adhesive label, located near the fuel connection of the equipment, specifically indicates the type of gas and the supply
pressure for which the equipment has been set up and tested.
Country
Category
Gas
Pressure
Gas
Pressure
AT
II2H3B/P
G20
20 mbar
G30/G31
50 mbar
BE <70kW
I2E(S)B, I3P
G20/G25
20/25 mbar
G31
37 mbar
CH
I2H
G20
20 mbar
DE
II2ELL3B/P
G20/G25
20 mbar
G30/G31
50 mbar
DK, FI, GR, SE, NO
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
ES, GB, IE, PT, SK
II2H3P
G20
20 mbar
G31
37 mbar
IT, CZ
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
FR
II2Esi3P
G20/G25
20/25 mbar
G31
37 mbar
LU
II2E3P
G20/G25
20 mbar
G31
37/50 mbar
HU
II2HS3B/P
G20/G25.1
25 mbar
G30/G31
30 mbar
CY, MT
I3B/P
G30/G31
30 mbar
EE, LT, SI, AL, MK
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
LV
I2H
G20
20 mbar
IS
I3P
G31
37 mbar
BG, RO, HR, TR
II2H3B/P
G20
20 mbar
G30/G31
30 mbar
PL
II2E3B/P
G20
20 mbar
G30/G31
37 mbar