AQUAKOND AKY 

CONDENSING BOILER

19

code HC0048.10GB ed.B-1811

AKY

the parameter scrolling speed is increased.  

To confirm a change in parameters, press ENTER for at least 

 

3 seconds. A change in the parameter is indicate by the display 

flashing.

All submenus can be scrolled from the bottom to the top, and they 

start over when the end of the menu is reached and vice versa.

4.2.3.  Entering the password

• 

From the initial screen (ON/OFF/rdy/FXX) use the ↑ (up arrow) 

and ↓ (down arrow) keys to reach the ABI function; hold down 

the ENTER key for 3 seconds;

• 

Set the password inside the ABI menu and confirm it with 

ENTER; hold it down for approximately 3 seconds (the 

flashing display will confirm that the parameter has been 

stored);

• 

Press ESC and, by using the ↑ and ↓ arrow keys, return 

to the initial screen (ON/OFF/rdy/FXX); press ENTER for 

3 seconds;

• 

Use the ↑ and ↓ arrow keys to reach the desired menu item 

(Flt, I/O, SET, PAR);

• 

Press ENTER to access the function;

• 

Use the ↑ and ↓ arrow keys to select the parameters to be 

displayed and edited;

• 

Press ENTER to display the parameter value;

• 

Use the ↑ and ↓ arrow keys to edit the value (only SET 

and PAR);

• 

Press ENTER to confirm the change made;

• 

To exit the parameter and the menu, press ESC until the 

initial screen is displayed (ON/OFF/rdy/FXX).

4.2.4.  Level 1 menu

The first level in the menu consists of the following items:

1.  machine status: ON, rdy, OFF;

2. 

FUn

, it allows to force the ON, OFF operation type; this menu 

can be accessed only in case of Stand-Alone configuration 

(ModBus address equal to Ø); when the address is different 

from Ø, this menu cannot be accessed;

3. 

rEg

, it allows to force the burner at minimum (Lo) or maximum 

(Hi) output in order to perform combustion tests; 

4. 

tin

, it shows the input voltage value (0/10Vdc) if the boiler 

is connected to a cascade management control unit;

5. 

PrA

, it shows water pressure inside the hydraulic circuit. It 

is used to load, and to control, the pressure inside the boiler 

and the hydraulic circuit. If the 01.6 value is displayed, the 

pressure inside the circuit is 1.60 bar;

6. 

Abi

. Entering the second or third level password allows to 

switch from the Abi menu to the underlying menus.

7. 

FRC 

allows to operate the circulator manually. Selecting 

the key for 3 sec will provide access to BLO submenu. 

Pressing the UAR key (up arrow ↑) starts the circulator. 

Releasing the UAR key (up arrow ↑) stops the circulator.

N

ote: To display water pressure value, press Enter when 

PrA is shown.

4.2.  LCD instrument panel

The instrument panel is fitted with a red 3-digit LCD display and 

with four function keys: 

 , 

 , 

ESC

 and 

ENTER

;

The screen allows the user to display the boiler operating mode, 

the Faults, water pressure inside the hydraulic circuit and the 

reading of probe values.

It also allows the service centre to change the main operating 

parameters.

Changing parameters requires a password.

4.2.1.  Viewing the machine status

The machine status is shown on the display by the following 

wordings:

rdy

  the machine is on without burner flame, it is waiting for the 

ON control and/or the heat demand from the thermostat

On

 

the machine is on with burner flame on;

OFF

  the machine has been switched off through the LCD 

control; any heat demands will be ignored. To light the 

boiler, the LCD must show the wording "operation ON";

Fxx

  Fault detected.

During normal operation, the display will show the wording 

On

 

if the burner is on; 

rdy 

when the boiler is being switched off or 

the room temperature has been reached.

If the boiler is connected to a SmartEASY/WEB, the PCB address 

must be set to a value different from Ø. In this case, every 30 

seconds and for the following 5 seconds, the display shows the 

PCB modbus address as Axx, where xx is the programmed address. 
In the event of communication problems between CPU-SMART 

PCB and LCD panel, the word 

CPU

 will flash on the display if 

the problem is caused by the CPU; three flashing dots will be 

displayed if the problem is caused by the display PCB.

If needs be, check that the display and the PCB are correctly 

connected and that the small cable RJ11 is securely held in 

the connector.

4.2.2.  Menu Navigation

The menu has three levels and all levels can be accessed in 

display mode. The first is accessible without entering a password, 

the second and third require entering passwords in write mode, 

as described in paragraph 4.2.5.

With modbus address other than Ø the following SETS can be 

edited: ST1, ST2, ST5, ST6.

If the boiler PCB is connected to a SmartEASY/WEB, and 

therefore with an address different from Ø, parameters can be 

viewed but cannot be modified.

The Service Centre that is required to use all menus must follow 

these instructions:

- disconnect the power supply;

- set the PCB address to Ø;

- restore power;

- after finishing the work, please remember to reset the switches 

to the previously set position.

Use the arrows to scroll the menus: UAR (up arrow ↑) and DAR 

(down arrow ↓). Press ENTER to select the menu, and again 

to select the parameter. Change the parameter with the arrows 

and confirm the change by pressing ENTER.

To exit the parameter or menu, press ESC. If you exit the 

programming function, after about 10 minutes the program 

will exit the menu and go back to the "machine status" display.

To change the parameter, press the arrow keys: pressing UAR 

↑ increases the parameter by 1, pressing DAR ↓ reduces it by 

1. When the arrow keys are pressed for at least three seconds, 

Содержание Aquakond AKY Series

Страница 1: ...Use Installation and Maintenance Manual AKY condensing boiler 1 code HC0048 10GB ed B 1811 AKY Energy Efficiency Class A NOx Class 6 Yield up to 109 Tax deduction Thermal Account for Public Authoriti...

Страница 2: ...AQUAKOND AKY CONDENSING BOILER 2 code HC0048 10GB ed B 1811 AKY...

Страница 3: ...as Appliance Regulation 2016 426 UE Direttive Rendimenti 92 42 CE Efficiency Requirements Directive 92 42 CE Regolamento UE 813 2013 EU Regulation 813 2013 Regolamento UE 811 2013 EU Regulation 811 20...

Страница 4: ...AQUAKOND AKY CONDENSING BOILER 4 code HC0048 10GB ed B 1811 AKY...

Страница 5: ...5 1 General Installation Instructions ITALY 20 5 2 Transport and Handling 20 5 3 Accessories for installation 21 5 4 Boiler installation 21 5 5 Electrical Connections 22 5 6 GAS Connections24 5 7 Con...

Страница 6: ...ficate supplied with this equipment The manufacturer declares that the equipment has been workmanlikemanufacturedincompliancewithUNI UNI CIG IEC EN technical standards and with all relevant legislatio...

Страница 7: ...ectrically powered equipment The following instructions must be followed do not touch the equipment with wet or damp parts of your body and or with bare feet do not use the gas pipes to earth electric...

Страница 8: ...al waste These operations facilitate recovery and recycling of the materials thus reducing the environmental impact NOTE All materials recovered will be processed and disposed of according to what pro...

Страница 9: ...e same time the combustion air flow and the fuel gas flow This technology increases the equipment safety as the gas valve suppliesthefuelaccordingtotheairflow basedonanadjustment presetinthefactory Un...

Страница 10: ...C kW 32 4 5 3 Useful heat output at 30 of load Hi 50 30 C P1 kW 10 Useful heat output Hi 72 45 C Pn kW 30 8 5 2 Useful efficiency Hi 80 60 C 4 96 5 96 7 Useful efficiency Hi 50 30 C 104 5 106 8 Usefu...

Страница 11: ...ut at 30 of load Hi 50 30 C P1 kW 11 4 15 7 21 0 31 1 Useful heat output Hi 72 45 C Pn kW 35 2 8 3 48 9 8 3 65 3 11 4 96 2 22 2 Useful efficiency Hi 80 60 C 4 98 3 98 2 96 8 95 7 97 5 97 4 96 7 98 6 U...

Страница 12: ...ithin 1 600 and 2 000 l h 70 flow rate within 1 800 and 2 000 l h 100 flow rate within 3 100 and 3 400 l h The boiler can operate correctly even with lower water flow rates in this case to reach the m...

Страница 13: ...volume multiply by 1 22 All data refer to a FERNOXALPHI11 monopropylene glycol and water mix recommended byAPEN GROUPforAQUAKOND systems Other types of glycol different from the recommended one inval...

Страница 14: ...ressure switch P system pump circulator PIT temperature inspection well PMIN PREX pressure probe PZI well for fuel cut off valve R3VIE 3 way control valve RBC filling tap TFUMI flue gas thermal fuse T...

Страница 15: ...rtificate No VS 319 00 safety thermostat TS 2BD NC contact thermostat opening T 90 3 C T P closing T 80 4 C IMQ CA02 02231 certified NOTE Water circuit test According to INAIL standard the boiler body...

Страница 16: ...0 070 AKY100 3 5 Boiler size Description Dimension 032 034 050 070 100 1 GAS SUPPLY G3 4 2 WATER RETURN G3 4 G1 G1 1 2 3 WATER DELIVERY G3 4 G1 G1 1 2 4 SAFETY VALVE G1 2 5 SAFETY VALVE G1 2 G1 2 6 SY...

Страница 17: ...es the heat output while keeping the delivery temperature fixed Boilerlockoutandreset availableinsideit canberemotely indicated with the APEN remote control code C09660 3 6 Operation and accessories T...

Страница 18: ...utessoastoeliminateanyresidualheatin the boiler water post circulation the fume fan too will continue toworkforapproximately15secondstocleanupthecombustion chamber combustion chamber post cleaning pha...

Страница 19: ...the user to display the boiler operating mode the Faults water pressure inside the hydraulic circuit and the reading of probe values It also allows the service centre to change the main operating para...

Страница 20: ...urrent regulations concerning design installation and maintenance of thermal systems Reference standards Ministerial Decree of 12 April 1996 containing the fire prevention rules for design constructio...

Страница 21: ...lly make sure that the boiler is slanted backwardsinordertofacilitatethe flow of condensate coming from the fume exhaust Alternatively insert a shim between the lower part of the boiler and the wall t...

Страница 22: ...dc CLK DAT NC IDC1 ID1 LBW Power supply plug YELLOW GREEN 5 5 Electrical Connections 5 5 1 Boiler power supply The boiler must be correctly connected to an effective earthing system fitted in complian...

Страница 23: ...AGND 5 5 3 Connecting SmartEASY WEB remote control TheSmartEASY WEBmustbeconnectedbyusingtheconnector provided Connect the power supply making sure polarity is correct Connect the Modbus RS485 networ...

Страница 24: ...degrees is already activated by default KEY 1 Main burner gas solenoid valve 2 Pressure stabiliser 3 Safety gas solenoid valve 4 Gas filter with small section installed in the gas valve 5 Gas tap sup...

Страница 25: ...inalshouldbepositionedtowards the front side of the boiler see drawing to the side to prevent fumes from condensing close to the wall thereby wetting it CERTIFIED pipes and terminals must be used WARN...

Страница 26: ...e installation sealed chamber is required proceed as follows create a hole 80 for AKY032 AKY034 AKY050 and AKY070 or 100 for AKY100 on top of the boiler close the air inlet inside the boiler by means...

Страница 27: ...pe must have an open type connection to make sure that any ice formed inside the external system does not prevent the condensation from being drained away In any case it is recommend that the longest...

Страница 28: ...raulic circuit especially if the boiler is installedhigherwithrespecttothecorrespondingfanheater See first level menu FRC Section 4 2 4 Water glycol mix restoration In the event of water leakage and o...

Страница 29: ...r indicates the type of gas the equipment has been set up for AKY070FR xxx0 0 indicates that the equipment has been tested and set up for natural gas G20 AKY070MT xxx1 1 indicates that the equipment h...

Страница 30: ...SURE mbar 25 min 20 max 30 for Germany 20 mbar GAS ORIFICE PLATE mm 7 8 9 4 12 5 CARBON DIOXIDE CO2 9 1 0 2 Qmax 9 1 0 2 Qmin 8 8 0 2 GAS CONSUMPTION 15 C 1013mbar m3 h 3 80 0 64 4 21 0 88 5 82 1 02 7...

Страница 31: ...connected to the boiler when power voltage is provided to the boiler and ID2 IDC2 contact is closed on boiler PCB the ignition cycle starts if APEN or Smart EASY WEB remote control is connected refer...

Страница 32: ...are no gas leaks When the burner is lit and working at maximum capacity verify that 1 thevalveintakepressurecorrespondstothevaluerequired for the type of gas that you are using 2 the combustion analys...

Страница 33: ...the programme automatically returns to the machine status Move using the menu arrows select the parameter or setpoint to be displayed with ENTER change the parameter by pressing the arrow keys to inc...

Страница 34: ...olutely necessary The antifreeze recommended by APEN FERNOX ALPHI 11 glycol serves as inhibitor and preserves the exchanger from oxidation Maintenance TheexperiencegatheredovertimeabouttheexchangerbyA...

Страница 35: ...t 0 255 b8 sec 30 Flame stabilisation time ignition 0 255 b9 sec 15 30 Combustion chamber post cleaning time FAN ON 0 255 b10 5 Motor rpm increase for each b11 seconds 1 100 b11 sec 2 Time interval fo...

Страница 36: ...h PT 0 0 140 001 H46 0 Flue gas temperature operation 0 modulation only 1 burner OFF TH3 C 103 Temperature upper limit autoreset if NTC3 TH3 0 140 Hydraulic circuit WATER PRESSURE control S5 3 1 Press...

Страница 37: ...nsecutive hours the TER equipment has performed a control cycle switching temporarily to stand by mode Auto reset F17 Internal malfunction of ACF equipment that does not accept reset command from CPU...

Страница 38: ...ircuit F80 No water pressure water pressure PRH ST5 P5 INAIL minimum pressure switch activation IPMIN forAKY100only If this happens frequently check the presence of leakages in water circuit Auto rese...

Страница 39: ...tion If SmartEASY WEB control is used use jumpers between ID2 IDC2 terminals All the controls mentioned operate as an ambient thermostat Component key ACF Flame monitoring equipment ACC Start up elect...

Страница 40: ...4 U3 F8 C56 R8 9 C 14 R 25 F2 R106 R7 7 R4 3 C 27 R4 9 R 10 R 58 C4 0 C 20 C 8 Q5 R 45 R 62 RL2 C 22 R 64 D3 C 23 CN01 LC1 R32 RL1 C51 U11 LC6 C1 1 R7 0 R4 1 R40 D9 D1 R3 5 R110 R 42 R31 R5 9 R9 6 TS1...

Страница 41: ...U3 F8 C56 R8 9 C 14 R 25 F2 R106 R7 7 R4 3 C 27 R4 9 R 10 R 58 C4 0 C 20 C 8 Q5 R 45 R 62 RL2 C 22 R 64 D3 C 23 CN01 LC1 R32 RL1 C51 U11 LC6 C1 1 R7 0 R4 1 R40 D9 D1 R3 5 R110 R 42 R31 R5 9 R9 6 TS1 R...

Страница 42: ...ETY VALVE C09322 TRANSDUCER C09730 C09735 01 W AT E R D E L I V E R Y TEMPERATURE PROBE G12064 POWER SUPPLY PLUG G12930 AKY032 034 050 070 G14456 AKY100 GAS VALVE C09280 GAS VALVE CABLE G16302 AKY032...

Страница 43: ...ON ELECTRODE C09313 IONISATION ELECTRODE GASKET C09255 IONISATION ELECTRODE CABLE C09257 START UP ELECTRODE C09312 START UP ELECTRODE GASKET C09254 START UP ELECTRODE CABLE C09309 BURNER FLANGE INSULA...

Страница 44: ...ns for the replacement of winter air conditioning systems the models of condensing gas boiler that it produces belonging to the range of AKY condensing boilers are classified in ClassA according to Re...

Отзывы: