Wiring a Signaling Line Circuit (SLC)
Installation
IQ-301 PN 50036:F 10/29/2001
47
Figure 27 shows typical wiring of a supervised and power-limited two-wire SLC that
meets NFPA 72 Style 4 requirements.
CAUTION: Terminate shield drain wire according to the instructions in “SLC
Shield Termination” on page 43.
Note: ISO-X devices are not required to meet NFPA Style 4. You can install a
maximum of 25 devices, detectors, and modules between isolator modules, or isolator
detector mounting base.
Figure 27 Two-wire SLC (Style 4)
!!
1 2 3 4
TB4
TB5
TB6
TX REF RX REF
OUT OUT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
2(+)
1(-)
3
LOOP
ADDRESS
TYPE
Low
Med
High
1
2
3
4
1
2
3
4
9
0
8
1
7
2
6
3
5
4
-
+
+
-
9
0
8
1
7
2
6
3
5
4
-
+
+
-
CPU
Connect (+) to TB 6-3
Connect (–) to TB 6-5
B710LP Detector Base
Use with FSP, FSI, and FST
Series intelligent detectors
Separate T-Tap to
other SLC devices
no connection
NBG-12LX
Monitor Module
Control or Relay
Module
Loop Isolator Module
Loop Isolator Module
A
F
P
200
-S
LC
-6.
cdr