How to Enter Program Change
Programming
IQ-301 PN 50036:F 10/29/2001
83
How to a Program a Control or Relay Module
A sample display of a typical control module Modify Point screen appears in Figure 67.
If editing the module while using the Modify Point option, you can modify all fields as
shown in Figure 67.
Figure 67 Sample Control or Relay Module Programming Screen
Press the
ENTER
key to accept default program information or press the
BACKSPACE
key
to reject the default autoprogram information. Edit any field in the LCD display by
following these steps:
1. Move the blinking cursor with the right cursor key to the field you want to edit.
2. Change blinking fields by pressing the up cursor key, or by pressing a numeric key.
Selection of control or relay module Type Code may change their function. Table 24
contains descriptions of the control or relay module Type Codes.
Table 24 Control or Relay Module Type Codes
Type Code Label
Special Function
CONTROL
None (default)
RELAY
Ignore open circuit
STROBE
CKT
None
BELL
None
HORN
CIRCUIT
None
AUDIBLE
CKT
None
BLANK
None, select when no other Type Code applies
RELEASE
CKT
Short = Normal (nonpower-limited, see Appendix D)
REL
CKT
ULC
Short = Trouble (supervised and power-limited, see Appendix D)
RELEASE
FORM
_
C
Contacts operated upon release
Note: A releasing circuit is always non-silenceable.
PROGRM@CONTROL
MODULE@ADDRESS@08
Z00@Z@@Z@@Z@@Z
@@@@@@@@@@@@@S*M08
“M” (Module) prefix to device
SLC address
Default zone selection is
Z00 (general alarm)
Walk Test (*) is not selected by
default. (To select, change to “W”)
Type Code (For explanations,
refer to Table 24)
CBE selections
Two-digit SLC address (01-99)
Silenceable (S) selected by
default. (* = not selected).
Custom label for this
device, which you can edit
using the programming
keys.