Specifications
System Overview
IQ-301 PN 50036:F 10/29/2001
27
1.11 Specifications
This section contains electrical specifications for the control panel.
1.11.1 Primary AC Power (TB7)
Primary AC connections are made through TB7 on the AUTOPULSE IQ-301.
Wire size: minimum 14 AWG with 600 VAC insulation.
•
IQ-301. 120 VAC, 50/60 Hz, 3.0 A
•
IQ-301E. 220/240 VAC, 50/60 Hz, 1.5 A
1.11.2 Battery (lead-acid only)
Maximum Charging Circuit
Dual Rate High Charge is 29.1 V @ 0.7 A
Normal Flat Charge is 27.6 V @ 0.5 A
Maximum Battery Capacity
18 AH. (Batteries larger than 12 AH require a BB-17
or other UL-listed battery cabinet.)
Minimum Battery Capacity
7 AH
1.11.3 Signaling Line Circuit (TB6)
Connections between the control panel and the Signaling Line Circuit (SLC) are
supervised and power-limited.
Voltage
24 VDC nominal, 27.6 VDC Max.
Maximum length
10,000 ft. (3048 m) per channel (NFPA Style 4) or
10,000 ft. (3048 m) total twisted-pair length (NFPA
Style 6 and 7)
Maximum loop current is
250 mA (max short circuit) or 100 mA (normal)
Maximum loop resistance
40 ohms
1.11.4 Notification Appliance and Releasing Circuits (TB2)
The following contains specifications for NACs and releasing circuits available on the
AUTOPULSE IQ-301 (all circuits are power-limited).
Max. wiring voltage drop
2 VDC
Normal Operating Voltage
24 VDC.
NAC circuit 1
2.5 A
NAC circuits 2-4
2.5 A shared total
Current for all external devices 5.0 A
Optional AVPS-24/AVPS-24E
Additional 3.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Optional APS-6R
Additional 6.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Max. signaling current/circuit
2.5 A
End-of-line resistor
4.7K, 1/2-Watt (PN 71252 UL-listed) for NACs)
Releasing circuits
REL-4.7K; for control module — REL-47K