Terminal Interface Protocol
Using the CRT-2 for Alter Status
174
IQ-301 PN 50036:F 10/29/2001
I.4.2 Accessing Alter Status Options
Access the Alter Status function from the CRT-2 by following these steps.
1. Turn on the CRT-2 connected to the control panel.
2. Press the Alter Status function key. The control panel displays the Alter Status
menu options:
3. Enter the Status Change Password. The factory default Status Change Password is
11111. The password does not display on the CRT-2. Five asterisks will appear in
place of the password:
The Alter Status Options menu appears:
From the Alter Status Options menu, you can select options 1-5.
I.4.3 Enable or Disable Detectors, Modules, or Bell Circuits
From the Alter Status menu, select Disable, option
1
. Disable lets you enable or disable
detectors, modules, or bell Circuits:
Enter the following:
1. Enter the first letter to read one of the following:
•
D
etector
•
M
odule
•
B
ell Circuit (NAC)
2. Enter the address or number of the device.
3. Press <Enter> and a display similar to the following will appear.
Enter Status Change Password or Escape to Abort
C
Press
*****
11111
W
Press
1=Disable 2=Sensitivity 3=Clear Verification 4=Clear History 5=Set Action/Alert
Disable/Enable D(Det.) / M(Mod.) / B(Bell ckt.), AA
1
Address or number
Press