IQ-301 PN 50036:F 10/29/2001
Table 23 contains a list of monitor module Type Codes:
Table 23 Monitor Module Type Codes
Type Code
Special function when activated
Nonlatching
or Latching
Activate
CBE?
MONITOR
(default)
Monitor module used to monitor normally open
contact, shorting-type devices.
latching
yes
PULL
STATION
NBG-12LX addressable manual pull station
latching
yes
SMOKE
DETECT
None
latching
yes
HEAT
DETECT
None
latching
yes
Blank
None, select when no other Type Code
applies.
latching
yes
WATERFLOW
Causes a non-silenceable alarm.
latching
yes
SUPERVISORY
Becomes a supervisory point (Refer to Section
4 “Operation”).
latching
yes
TAMPER
Becomes a supervisory point (Refer to Section
4 “Operation”).
latching
yes
NON
FIRE
A special non-alarm point used for energy
management or other non-fire situations
(Refer to Section 4 “Operation”)
nonlatching
yes
HAZARD
ALERT
A special non-alarm point used for monitoring
critical processes or other hazardous
situations, such as a tornado (Refer to Section
4 “Operation”).
latching
yes
FIRE
CONTROL
A special non-alarm point used for air handler
shutdown and are intended to override normal
operating automatic functions (Refer to
Section 4 “Operation”).
nonlatching
yes
ABORT
SWITCH
Aborts activation of a releasing zone (Refer to
Appendix D “Releasing Applications.”)
nonlatching
yes
MAN
.
RELEASE
Provide a manual release function and
overrides the abort switch (Refer to Appendix
D “Releasing Applications.”)
latching
yes
SILENCE
Functions like the Alarm Silence switch.
latching
no
SYSTEM
RESET
Functions like the System Reset switch.
nonlatching
no
EVACUATE
Functions like the Drill switch
latching
yes
PAS
INHIBIT
Overrides a Presignal selection (Refer to
Appendix H “Special Zones.”)
nonlatching
no
TROUBLE
MON
Short = Trouble (Refer to Section 3
“Programming” & Section 4 “Operation”).
latching
yes
BURGLAR
ALA
Causes Security Alarm on open or short
(Refer to Appendix E “Combination
Fire/Burglary Applications.”)
latching
yes