CNC Motion Setup/Testing Utility
P/N 70000634C
Setting the Signal Gain (F7)
1. Press
SigGain
(
F7
) to perform the signal gain test for the selected
amplifier.
2. Select
2
for the time (i.e., 2 seconds). Refer to
Figure 16
. The
following screen will be displayed:
4200SIGGAIN
Figure 16, Signal Gain Test Screen, AC Systems
IMPORTANT: Steps 9–13 apply only to ANILAM brushless AC
amplifiers. For other amplifiers, refer to the manufactures
guidelines to set the signal gain in the amplifier.
3. Use the keypad up and down
ARROW
keys to change the signal gain
until
FEED:
reads: 20.0 or 10% of Rapid.
4. To cancel the signal gain test, press
MANUAL
(
F4
); otherwise, press
Misc
(
F9
) to display the Miscellaneous Menu.
5. Select
Save Amp Settings
to save the amplifier settings to the
amplifier.
6. Press
Misc
(
F9
) to display the Miscellaneous Menu
7. Select
BackUp Amp Settings
to backup the amplifier settings to a file
on the CNC. The backup filename is DIGAMP-*.BK where ‘*’ is the
selected axis name (i.e., X, Z). This file is stored on the hard disk
drive.
8. Repeat steps in “Setup Parameter Verification,” “Setting the Balance
(F6),” and “Setting the Signal Gain (F7)” for each amplifier axis.