SFLR SP DISPLAY OPT
[ NOT DISPLAYED ]
[ IN CONTINUOUS MODE ]
[ IN SEQUENTIAL MODE ]
[ IN BOTH MODES ]
ÿü
to change,
õö
to choose,
ÿþ
to save
Definition: This parameter, if active, allows the current Setpoint of the PID
controller associated with the Hot Water to be displayed.
ÿø
TO ADVANCE TO NEXT SELECTION
NOTE: SFL2 functions allow for a second On/Off or PID control output. This function is NOT
utilized on typical Pasteurization loops.
SFLR ALARM1 TYPE
[ NONE/OFF ]
[LOW SIGNAL/VALUE ]
[HIGH RATE/VALUE ]
ÿü
to change,
õö
to choose,
ÿþ
to save
Definition: MUST remain at “High Rate/Value” selection for proper
utilization as “Loss of Signal” alarm. Causes Alarm 1 relay to
be failsafe active when above “Loss of Signal” setpoint.
Below Loss of Signal setpoint condition will cause relay to
open, sending fault signal to Legal Flow Controller. Will
result in system divert to balance tank.
ÿø
TO ADVANCE TO NEXT SELECTION
Revision 3.0
Section 5
31