2.5.3.
Hot Product Probe Input Board Wiring
The Hot Product Probe will always terminate at the bottom (furthest in) input card. The wiring terminal
block of this board has been color coded so as to differentiate it from the remaining cards. Termination’s
to the Hot Product Probe are as follows:
JU15
JU16
JU2
JU5
JU
3
JU6
JU7
JU8
BL
U
E
BL
A
C
K
BR
O
W
N
WH
IT
E
RE
D
GR
EEN
TB1
TB2
Figure 6 - Hot Product Input Card Wiring
All conditioning jumpers have been pre-set at the factory. Proper positions have been noted on the above
diagram.
2.5.4.
Hot Product Probe Wiring
The Hot Product Sensor is provided with dual removable plugs and a specified amount of six conductor
shielded cable. If wires are removed for installation purposes, they must be re-wired properly.
CAUTION: Anderson does not recommend splicing of signal cable. The possibility will exist for
corrosion, leading to intermittent connection or loss of signal. If cable length is insufficient, it is
recommended that a new, longer, cable be utilized.
VIBRATION DAMPENER - DO NOT DISCARD: A small black rubber puck was shipped with the Hot
Product Probe. It is inside the conduit housing of the sensor, and must be removed for wiring. This puck
prevents terminal blocks from coming loose in high vibration applications. RE-INSTALL upon
completion of probe wiring.
Once all wiring has been completed, a
Health Autho ity Seal must be placed from the cap (hole provided)
around the seal-tight grommet. This will prevent unauthorized entry into the Hot Product Probe.
r
Revision 3.0
Section 2
6