Panel Calibration
43
NXD/T-1200V Wall/Flush Mount Touch Panel
Panel Calibration
Overview
This section outlines the steps for calibrating the touch panel.
It is recommended that you calibrate the panel before its
initial use and after completing a firmware download.
Modero panels are factory setup with specific demo touch panel pages. The first splash screen that appears indicates the
panel is receiving power, beginning to load firmware, and preparing to display the default touch panel pages. When the
panel is ready, the AMX Splash Screen is replaced by the Initial Panel Page (FIG. 46).
Calibrating the Modero Panel
1.
Press and hold the grey Front Setup Access button (FIG. 47) for
6 seconds
(passing-over the Setup page) to access
the Calibration setup page (FIG. 48).
The panel should first be calibrated properly.
Press the crosshairs (on the Calibration page) to set the calibration points on the LCD (FIG. 48).
FIG. 46
AMX splash screen and initial Panel Page
FIG. 47
Location of grey Front Setup Access button
AMX Splash Screen
(appears during power-up)
Initial Panel Page
(AMX Logo Page)
Front Setup
Access button (grey)
- 3 second press/hold:
Accesses the Setup page
- 6 second press/hold:
Accesses the Calibration page
Single press puts the panel to sleep
Содержание Modero NXD-1200V
Страница 40: ...Touch Panel Accessories 28 NXD T 1200V Wall Flush Mount Touch Panel...
Страница 80: ...Configuring Communication 68 NXD T 1200V Wall Flush Mount Touch Panel...
Страница 92: ...Upgrading Modero Firmware 80 NXD T 1200V Wall Flush Mount Touch Panel...
Страница 164: ...Programming 152 NXD T 1200V Wall Flush Mount Touch Panel...
Страница 170: ...Appendix 158 NXD T 1200V Wall Flush Mount Touch Panel...
Страница 175: ...Troubleshooting 163 NXD T 1200V Wall Flush Mount Touch Panel...