Troubleshooting
4-7
Drive does not respond to changes in speed command.
Motor and/or drive will not accelerate to commanded speed.
Cause(s)
Indication
Corrective Action
No value is coming from the
source of the command.
The drive “Run” indicator is lit
and output is 0 Hz.
•
[Control Source] for
correct source.
•
If the source is an analog input,
check wiring and use a meter to
check for presence of signal.
•
[Commanded Freq]
to verify correct command.
Incorrect reference source is
being selected via remote
device or digital inputs.
None
•
[Control Source] for
correct source.
•
[Contrl In Status] to
see if inputs are selecting an
alternate source. Verify settings
for
[Digital Inx Sel].
•
[Speed Reference]
for the source of the speed
reference. Reprogram as
necessary.
•
Review the Speed Reference
Control chart on
Cause(s)
Indication
Corrective Action
Acceleration time is excessive. None
Reprogram
[Accel Time 1] or
[Accel Time 2].
Excess load or short
acceleration times force the
drive into current limit, slowing
or stopping acceleration.
None
Compare
[Output Current] with
[Current Limit 1].
Remove excess load or reprogram
[Accel
Time 2].
Check for improper
[Boost
Select] setting.
Speed command source or
value is not as expected.
None
Verify
[Commanded Freq].
[Control Source] for the
proper Speed Command.
Programming is preventing the
drive output from exceeding
limiting values.
None
[Maximum Freq] to
insure that speed is not limited by
programming.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......