Troubleshooting
4-5
Motor does not Start.
F122 I/O Board Fail
➁
Failure has been detected in the
drive control and I/O section.
1. Cycle power.
2. Replace drive if fault cannot be
cleared.
(1)
for a description of fault types.
No.
Fault
Ty
p
e
(1
)
Description
Action
Common Symptoms and Corrective Actions
Cause(s)
Indication
Corrective Action
No output voltage to the motor.
None
Check the power circuit.
•
Check the supply voltage.
•
Check all fuses and disconnects.
Check the motor.
•
Verify that the motor is
connected properly.
Check the control input signals.
•
Verify that a Start signal is
present. If 2-Wire control is used,
verify that either the Run
Forward or Run Reverse signal
is active, but not both.
•
Verify that I/O Terminal 01 is
active.
•
[Start Source]
matches your configuration.
•
[Reverse
Disable] is not prohibiting
movement.
Drive is Faulted
Flashing red status light
Clear fault.
•
Press Stop
•
Cycle power
•
Set
[Fault Clear] to option 1
“Clear Faults”.
•
Cycle digital input if
[Digital Inx Sel] is set to option 7
“Clear Fault”.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......