Programming and Parameters
3-9
Basic Program Group
(continued)
P037 [Stop Mode]
Related Parameter(s):
,
,
Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important:
I/O Terminal 01 is always a coast to stop input except when
[Start Source] is set for
“3-Wire” control. When in three wire control, I/O Terminal 01 is controlled by
[Stop Mode].
Hardware Enable Circuitry
By default, I/O Terminal 01 is a coast to stop input. The status of the input is interpreted by drive
software. If the application requires the drive to be disabled without software interpretation, a
“dedicated” hardware enable configuration can be utilized. This is accomplished by removing the
ENBL enable jumper on the control board. See
for details. In this case, the drive will always
coast to a stop regardless of the settings of
[Start Source] and
[Stop Mode].
Options
0
“Ramp, CF”
(1)
Ramp to Stop. “Stop” command clears active fault.
1
“Coast, CF”
(Default) Coast to Stop. “Stop” command clears active fault.
2
“DC Brake, CF”
DC Injection Braking Stop. “Stop” command clears active
fault.
3
“DCBrkAuto,CF”
DC Injection Braking Stop with Auto Shutoff.
•
Standard DC Injection Braking for value set in
Brake Time].
OR
•
Drive shuts off if the drive detects that the motor is
stopped.
“Stop” command clears active fault.
4
“Ramp”
Ramp to Stop.
5
“Coast”
Coast to Stop.
6
“DC Brake”
DC Injection Braking Stop.
7
“DC BrakeAuto”
DC Injection Braking Stop with Auto Shutoff.
•
Standard DC Injection Braking for value set in
Brake Time].
OR
•
Drive shuts off if the drive detects that the motor is
stopped.
(1)
Stop input also clears active fault.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......