D-12
Application Notes
Example 1
One External Motor without AutoSwap
•
Auxiliary Motor Control is enabled via Parameter
[Aux Motor Mode].
•
Number of auxiliary motors is set via Parameter
[Aux Motor Qty].
•
Relays are configured for Auxiliary Motor Control via parameters
, and
•
The frequency of Motor #1 that Motor #2 turns on at is set via Parameter
[Aux 1 Start Freq].
•
The time that Motor #1 is above the value set by
[Aux 1 Start Freq]
before turning on Motor #2 is set via Parameter
[Aux Start Delay].
•
The frequency of Motor #1 that Motor #2 turns off at is set via Parameter
[Aux 1 Stop Freq].
•
The time that Motor #1 is below the value set by
[Aux 1 Stop Freq]
before turning off Motor #2 is set via Parameter
[Aux Stop Delay].
•
PID setup is done via Parameters
through
. See Appendix D for
additional information.
Important:
If using auxiliary motor control, ensure that wiring and parameter
configuration are correct before wiring contactor outputs. All relays
on the Auxiliary Relay Card will energize on power-up by default.
Failure to verify proper wiring and parameter configuration can result
in improper motor operation or drive damage.
PID
Reference
Feedback
Drive Relays
Auxiliary Relay Card
M2L
PowerFlex 400
Three-Phase Power
M2L
M1
M2
Frequency
R241 [Aux 1 Start Freq]
R251 [Aux Stop Delay]
R250 [Aux Start Delay]
R242 [Aux 1 Stop Freq]
Time
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......