1-28
Installation/Wiring
Essential Requirements for CE Compliance
Conditions 1-4 listed below
must be
satisfied for PowerFlex drives to
meet the requirements of
EN61800-3
.
1.
Grounding as described in
for
additional grounding recommendations.
2.
Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
3.
All shielded cables should terminate with the proper shield
connector.
4.
Table 1.J PowerFlex 400 – EN61800-3 Compliance
PowerFlex 400 Drive First Environment Restricted
First Environment Unrestricted
kW (HP) Cat. No.
22C-…
Required Filter
(Allen-Bradley)
Restrict
Motor
Cable to
(Meters)
Install
Drive and
Filter in
Shielded
Enclosure
Required Filter
Restrict
Motor
Cable to
(Meters)
Install
Drive and
Filter in
Shielded
Enclosure
200-240 Volts
2.2 (3.0) B012N103 22-RF034-CS 10
No
22-RF034-CS
1
Required
3.7 (5.0) B017N103 22-RF034-CS 10
No
22-RF034-CS
1
Required
5.5 (7.5) B024N103 22-RF034-CS 10
No
22-RF034-CS
1
Required
7.5 (10)
B033N103 22-RF034-CS 10
No
22-RF034-CS
1
Required
11 (15)
B049A103 22-RFD070
150
Required
Deltron MIF Series 50
Required
15 (20)
B065A103 22-RFD100
150
Required
Deltron MIF Series 50
Required
18.5 (25) B075A103 22-RFD100
150
Required
Deltron MIF Series 50
Required
22 (30)
B090A103 22-RFD150
150
Required
Deltron MIF Series 50
Required
30 (40)
B120A103 22-RFD150
150
No
Deltron MIF Series 50
Required
37 (50)
B145A103 22-RFD180
150
No
Deltron MIF Series 75
Required
380-480 Volts
2.2 (3.0) D6P0N103 22-RF018-CS 10
No
22-RF018-CS
1
Required
4.0 (5.0) D010N103 22-RF018-CS 10
No
22-RF018-CS
1
Required
5.5 (7.5) D012N103 22-RF018-CS 10
No
22-RF018-CS
1
Required
7.5 (10)
D017N103 22-RF018-CS 10
No
22-RF018-CS
1
Required
11 (15)
D022N103 22-RF026-CS 10
No
22-RF026-CS
1
Required
15 (20)
D030N103 22-RFD036
100
No
Deltron MIF Series 5
Required
18.5 (25) D038A103 22-RFD050
150
No
Deltron MIF Series 5
Required
22 (30)
D045A103 22-RFD050
150
No
Deltron MIF Series 5
Required
30 (40)
D060A103 22-RFD070
50
No
Deltron MIF Series 5
Required
37 (50)
D072A103 22-RFD100
50
No
Deltron MIF Series 5
Required
45 (60)
D088A103 22-RFD100
50
No
Deltron MIF Series 5
Required
55 (75)
D105A103 22-RFD150
150
No
Deltron MIF Series 5
Required
75 (100) D142A103 22-RFD180
50
No
Deltron MIF Series 5
Required
90 (125) D170A103
Consult Factory
Consult Factory
110 (150) D208A103
Consult Factory
Consult Factory
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......