Start Up
2-7
Local/Remote Mode
In Local mode:
•
Start command and speed reference come from the integral keypad
Start/Hand and Digital Speed Increment and Decrement keys.
•
Auto key stops the drive and the drive switches to Remote mode.
Important:
If the drive is running and P036 [Start Source] = 3 or 6
(2-Wire Control), the drive will continue to run at reference
defined by P038 [Speed Reference] if a valid start
command is present.
In Remote mode:
•
Auto key LED is illuminated.
•
Start command is defined by
[Start Source].
•
Speed Reference command is defined by
[Speed Reference].
•
Auto key stops the drive and the drive switches to Local mode.
Table 2.B P042 [Auto Mode]
=
2 “Local/Remote”
T051-T054 [Digital Inx Sel]
≠
2 “Auto Mode” or 3 “Local”
Important:
Certain digital input settings can override drive operation.
Refer to
Start and Speed Reference Control on page 1-24
for details.
Local Mode
Remote Mode
Key
LED Key Function
LED Key Function
On Starts drive.
Runs according to Speed Increment/
Decrement keys.
Off Not active.
Only active if P036 [Start Source] =
0 “Keypad”. Starts drive.
On Changes speed.
Off Not active.
Keys are only active if P038 [Speed
Source] = 0 “Drive Pot”.
Off Stops drive and changes to Remote
Mode.
On Stops drive and changes to Local
Mode.
N/A Stops drive.
N/A Stops drive.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......