T070 [Analog In 1 Lo]
Related Parameter(s):
,
,
Stop drive before changing this parameter.
Sets the analog input level that corresponds to
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than T071 [Analog In 1 Hi].
Important:
If analog inversion is implemented the drive will go to maximum frequency in the event the
analog input is lost. It is strongly recommended to activate T072 [Analog In 1 Loss] to protect from this
potential occurrence.
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]
0
Speed Reference
T071 [Analog In 1 Hi]
Related Parameter(s):
,
,
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than T070 [Analog In 1 Lo].
Values
Default:
100.0%
Min/Max:
0.0/100.0%
Display:
0.1%