Programming and Parameters
3-19
Terminal Block Group
(continued)
T066 [Opto Out Level]
,
32 bit parameter.
Determines the on/off point for the opto output when
[Opto Out Sel] is set to option 6, 7, 8, 9, 10
or 12.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
32
T065 Setting
T066 Min/Max
6
7
8
9
10
12
0/400 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1
T068 [Opto Out Logic]
Related Parameter(s):
Determines the logic (Normally Open/NO or Normally Closed/NC) of the opto output.
Note
: Setting output to NC may cause output to “glitch” on power-up. The off/reset state of all outputs
is open.
Values
Default:
0
Min/Max:
0/1
Display:
1
T068 Option
Opto Out Logic
0
1
NO (Normally Open)
NC (Normally Closed)
T069 [Analog In 1 Sel]
,
Sets the analog input signal mode (0-20mA, 4-20mA, or 0-10V). This parameter must match DIP
Switch AI1 setting on the control board.
Values
Default:
2
Min/Max:
0/6
Display:
1
T069 Option
Setting
Input Range
DIP Switch AI1 Setting
0
Current Mode
0-20 mA
20 mA
1
Current Mode
4-20 mA
20 mA
2
Voltage Mode - Unipolar
0-10V
10V
4
Current Mode (Square Root)
0-20 mA
20 mA
5
Current Mode (Square Root)
4-20 mA
20 mA
6
Voltage Mode - Unipolar (Square Root) 0-10V
10V
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......