3-18
Programming and Parameters
Terminal Block Group
(continued)
T065 [Opto Out Sel]
,
Determines the operation of the programmable opto output.
Options
0
“Ready/Fault”
Opto output is active when power is applied. This indicates
that the drive is ready for operation. Opto output is inactive
when power is removed or a fault occurs.
1
“At Frequency”
(Default)
Drive reaches commanded frequency.
2
“MotorRunning”
Motor is receiving power from the drive.
3
“Hand Active”
Active when drive is in local control.
4
“Motor Overld”
Motor overload condition exists.
5
“Ramp Reg”
Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.
6
“Above Freq”
•
Drive exceeds the frequency (Hz) value set in
[Opto
Out Level].
•
Use T066 to set threshold.
7
“Above Cur”
•
Drive exceeds the current (% Amps) value set in
[Opto Out Level].
•
Use T066 to set threshold.
Important:
Value for
[Opto Out Level] must be entered
in percent of drive rated output current.
8
“Above DCVolt”
•
Drive exceeds the DC bus voltage value set in
[Opto
Out Level].
•
Use T066 to set threshold.
9
“Above Anlg 2”
•
Analog input voltage (I/O Terminal 17) exceeds the value
set in
[Opto Out Level].
•
Do not use if
[Analog In 2 Sel] is set to 3 “Voltage
Mode - Bipolar”.
•
This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 17) is wired to a
PTC and external resistor.
•
Use T066 to set threshold.
10
“Above PF Ang”
•
Power Factor angle has exceeded the value set in
[Opto Out Level].
•
Use T066 to set threshold.
11
“Anlg In Loss”
Analog input loss has occurred. Program
[Analog In 1
Loss] and/or
[Analog In 2 Loss] for desired action when
input loss occurs.
12
“ParamControl”
Enables the output to be controlled over network
communications by writing to
[Opto Out Level].
(0 = Off, 1 = On.)
13
“Retries Exst”
Value set in
[Auto Rstrt Tries] is exceeded.
14
“NonRec Fault”
•
Number of retries for
[Auto Rstrt Tries] is exceeded
OR
•
Non-resettable fault occurs
OR
•
[Auto Rstrt Tries] is not enabled.
15
“Reverse”
Drive is commanded to run in reverse direction.
16
“Logic In 1”
An input is programmed as “Logic In 1” and is active.
17
“Logic In 2”
An input is programmed as “Logic In 2” and is active.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......