1-24
Installation/Wiring
The drive speed command can be obtained from a number of different sources. The source is
normally determined by
[Speed Reference]
. The drive Start command is normally
determined by
[Start Source].
However, the settings for these parameters can be
overridden by a variety of methods. See the chart below for the override priority.
Start and Speed Reference Control
Purge Input
Enabled and Active:
[Digital Inx Sel] = 1
Local Input
Enabled and Active
[Digital Inx Sel] = 3
No
Yes
Start, Speed and Direction commands
come from Integral Keypad.
Direction is Forward unless an input is
programmed for "Keypad/Jog Direction"
Auto Input
Enabled and Active
[Digital Inx Sel] = 2
No
Yes
Run as specified by
P038 [Speed Reference].
Start and Direction commands
come from P036 [Start Source].
Comm Select Input
Enabled and Active:
[Digital Inx Sel] = 4
No
Yes
Start, Speed and Direction commands
come from RS485 (DSI) port.
Drive is in
Hand/Local Mode
selected by AUTO key
(1)
No
Yes
Start and Speed commands
come from Integral Keypad.
Direction is Forward unless an input is
programmed for "Cmd Reverse"
Analog Input 1
Override Enabled & Active:
[Digital Inx Sel] = 14
Analog Input 2
Override Enabled & Active:
[Digital Inx Sel] = 15
No
Yes
Speed commands come from
Analog Input 1 (I/O Terminal 13).
Start and Direction
follows P036 [Start Source].
Speed commands come from
Analog Input 2 (I/O Terminal 17).
Start and Direction
follows P036 [Start Source].
No
Yes
P038 [Speed Reference]
= 4 or 5
No
Yes
Run as specified by
P038 [Speed Reference].
Start and Direction commands come
from P036 [Start Source].
Run as specified by
A144-A146 [Preset Freq 1-3].
Start follows P036 [Start Source],
Direction follows
Preset Frequency settings.
Preset Inputs Active
T051/T052/T053 = 8
No
Yes
Run as specified by
A152 [PID Ref Sel].
Start and Direction commands come
from P036 [Start Source].
PID Enabled:
A152 [PID Ref Sel] ¹ 0
No
Yes
Run as specified by
P038 [Speed Reference].
Start and Direction commands come
from P036 [Start Source].
No
Yes
Drive will Start and Run as
specified by A141 [Purge Frequency].
Direction is always Forward.
(1)
for additional
information on the operation of
the Hand/Auto Mode.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......