3-8
Programming and Parameters
Basic Program Group
(continued)
P036 [Start Source]
Related Parameter(s):
Stop drive before changing this parameter.
Sets the control scheme used to start the drive when in Auto/Remote mode.
Refer to
Start and Speed Reference Control on page 1-24
for details about how other drive settings
can override the setting of this parameter.
Important:
For all settings except options 3 and 6, the drive must receive a leading edge from the
start input for the drive to start after a stop input, loss of power or fault condition.
Options
0
“Keypad”
Integral keypad controls drive operation.
•
I/O Terminal 01 = Stop: Coast to Stop
•
I/O Terminal 02 = Not Used
•
I/O Terminal 03 = Not Used
1
“3-Wire”
I/O Terminal Block controls drive operation.
•
I/O Terminal 01 = Stop: Per
[Stop Mode]
•
I/O Terminal 02 = Start
•
I/O Terminal 03 = Direction
2
“2-Wire”
I/O Terminal Block controls drive operation.
•
I/O Terminal 01 = Stop: Coast to Stop
•
I/O Terminal 02 = Run FWD
•
I/O Terminal 03 = Run REV
3
“2-W Lvl Sens”
(Default)
I/O Terminal Block controls drive operation.
•
I/O Terminal 01 = Stop: Coast to Stop
•
I/O Terminal 02 = Run FWD
•
I/O Terminal 03 = Run REV
Drive will restart after a “Stop” command when:
•
Stop is removed and Run FWD is held active
4
“2-W Hi Speed”
I/O Terminal Block controls drive operation.
•
I/O Terminal 01 = Stop: Coast to Stop
•
I/O Terminal 02 = Run FWD
•
I/O Terminal 03 = Run REV
Outputs are kept in a ready-to-run state. The drive will
respond to a “Start” command within 10 ms.
Important:
There is greater potential voltage on the output
terminals when using this option.
5
“Comm Port”
Remote communications controls drive operation.
•
I/O Terminal 01 = Stop: Coast to Stop
•
I/O Terminal 02 = Not Used
•
I/O Terminal 03 = Not Used
6
“2-W Lvl/Enbl”
I/O Terminal Block controls drive operation.
•
I/O Terminal 01 = Function Loss: Fault and Coast to Stop
•
I/O Terminal 02 = Run FWD
•
I/O Terminal 03 = SW Enable
Drive will restart after a “Stop” command when:
•
Stop is removed and Run FWD is held active
!
See Attention
Below
!
See Attention
Below
!
ATTENTION:
Hazard of injury exists due to unintended operation. When
P036 [Start Source] is set to option 3 or option 6, and the Run input is
maintained, the Run inputs do not need to be toggled after a Stop input or a
fault clear for the drive to run again. The drive will stop only when the stop
command is maintained or the drive is faulted.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......