3-52
Programming and Parameters
Advance Display Group
d301 [Control Source]
Related Parameter(s):
,
Displays the active source of the Start Command and Speed Command which are normally defined
by the settings of
[Start Source] and
[Speed Reference] but may be overridden by digital
inputs. Refer to the flowcharts on pages
and
for details.
Values
Default:
Read Only
Min/Max:
0/99
Display:
1
Start Command
Digit 0
0 = Keypad
1 = Terminal Block
2 = Communications
Speed Command
Digit 1
0 = Local Keypad Potentiometer
1 =
[Internal Freq]
2 = Analog Input 1
3 = Analog Input 2
4 =
[Preset Freq x]
(
[Digital Inx Sel] must be set to 4)
5 = Communications
Reserved
Digit 2
Reserved
Digit 3
d302 [Contrl In Status]
Related Parameter(s):
,
Status of the control terminal block control inputs.
Important:
Actual control commands may come from a source other than the control terminal block.
Values
Default:
Read Only
Min/Max:
0/1
Display:
1
1 = Condition True, 0 = Condition False
Start/FWD In
I/O Terminal 02
Dir/REV In
I/O Terminal 03
Stop Input
I/O Terminal 01
Digital In 1
I/O Terminal 05
Digital In 2
I/O Terminal 06
Digital In 3
I/O Terminal 07
Digital In 4
I/O Terminal 08
Not Used
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......