Programming and Parameters
3-31
Advanced Program Group
A141 [Purge Frequency]
Related Parameter(s):
,
,
Provides a fixed frequency command value when T051-T054 [Digital Inx Sel] is set to 1 “Purge”. An
active purge input will override speed command as shown in the flowchart on
.
Values
Default:
5.0 Hz
Min/Max:
0.0/320.0 Hz
Display:
1.0 Hz
A142 [Internal Freq]
Related Parameter(s):
,
Provides the frequency command to the drive when
[Speed Reference] is set to 1 “Internal
Freq”. When enabled, this parameter will change the frequency command in “real time” using the
digital speed keys when in program mode.
Important:
Once the desired command frequency is reached, the Enter key must be pressed to store
this value to EEPROM memory. If the ESC key is used before the Enter key, the frequency will return
to the original value following the normal accel/decel curve.
If
[Digital Inx Sel] is set to 16 “MOP Up” or 17 “MOP Down” this parameter acts as the
MOP frequency reference if
[Speed Reference] is set to 1 “InternalFreq”.
Values
Default:
60.00 Hz
Min/Max:
0.00/320.00 Hz
Display:
0.01 Hz
A143 [Preset Freq 0]
(1)
A144 [Preset Freq 1]
A145 [Preset Freq 2]
A146 [Preset Freq 3]
Related Parameter(s):
,
Values
A143 Default:
(1)
A144 Default:
A145 Default:
A146 Default:
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
Min/Max:
0.0/320.0 Hz
Display:
0.1 Hz
Provides a fixed frequency command value when
[Digital Inx Sel] is set to 8 “Preset
Freq”.
An active preset input will override speed command as shown in the flowchart on page
(1)
To activate A143 [Preset Freq 0] set
[Speed Reference] to option 4 “Preset Freq”.
Input State
of Digital In 1
(I/O Terminal 05
when T051 = 8)
Input State
of Digital In 2
(I/O Terminal 06
when T052 = 8)
Frequency Source
Accel / Decel Parameter Used
(2)
0
0
A143 [Preset Freq 0]
[Accel Time 1] / [Decel Time 1]
1
0
A144 [Preset Freq 1]
[Accel Time 1] / [Decel Time 1]
0
1
A145 [Preset Freq 2]
[Accel Time 2] / [Decel Time 2]
1
1
A146 [Preset Freq 3]
[Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides
the settings in this table.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......