Programming and Parameters
3-41
Advance Program Group
(continued)
A178 [DC Brk Time@Strt]
Related Parameter(s):
,
Sets the length of time that DC brake current is “injected” into the motor after a valid start command is
received. Parameter
[DC Brake Level] controls the level of braking current used.
Values
Default:
0.0 Secs
Min/Max:
0.0/99.9 Secs (A setting of 99.9 = Continuous)
Display:
0.1 Secs
Volts/Speed
Time
Start Command
[DC Brake Level]
[DC Brk Time@Strt]
Voltage
Speed
A179 [Current Limit 1]
Related Parameter(s):
Maximum output current allowed before current limiting occurs.
Values
Default:
Drive Rated Amps
×
1.1
Min/Max:
0.0/(Drive Rated Amps
×
1.5)
Display:
0.1 Amps
A180 [Current Limit 2]
Related Parameter(s):
Maximum output current allowed before current limiting occurs.
Values
Default:
Drive Rated Amps
×
1.1
Min/Max:
0.0/(Drive Rated Amps
×
1.5)
Display:
0.1 Amps
A181 [Motor OL Select]
Related Parameter(s):
,
Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I
2
t
overload function.
Options
0
“No Derate” (Default)
1
“Min Derate”
2
“Max Derate”
Min Derate
0
80
100
60
40
20
No Derate
0
80
100
60
40
20
%
of P033
[Motor OL Curent
]
Max Derate
0
80
100
60
40
20
0
200
175
150
125
100
75
50
25
0
200
175
150
125
100
75
50
25
0
200
175
150
125
100
75
50
25
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......