Programming and Parameters
3-45
Advance Program Group
(continued)
A194 [Compensation]
Enables/disables correction options that may improve problems with motor instability.
Options
0
“Disabled”
1
“Electrical” (Default)
(1)
Some drive/motor combinations have inherent instabilities
which are exhibited as non-sinusodial motor currents. This
setting attempts to correct this condition.
2
“Mechanical”
Some motor/load combinations have mechanical resonances
which can be excited by the drive current regulator. This
setting slows down the current regulator response and
attempts to correct this condition.
3
“Both”
(1)
Use “Dead Time Compensation” algorithm to minimize flat spots in motor current waveforms. Use
this solution also to achieve motor stability.
A195 [Reset Meters]
Related Parameter(s):
-
Resets the marker that indicates Fault Times and Energy usage.
Options
0
“Ready/Idle” (Default)
1
“Reset MWh”
Also resets kWh marker.
2
“Reset Time”
min, hr, and x10hr
A196 [Testpoint Sel]
Related Parameter(s):
Used by Rockwell Automation field service personnel.
Values
Default:
1024
Min/Max:
1024/65535
Display:
1
A197 [Fault Clear]
Related Parameter(s):
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options
0
“Ready/Idle” (Default)
1
“Reset Fault”
2
“Clear Buffer”
Clears all fault buffers.
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......