Programming and Parameters
3-5
Basic Display Group
(continued)
b006 [Drive Status]
Related Parameter(s):
Present operating condition of the drive.
Values
Default:
Read Only
Min/Max:
0/1
Display:
1
1 = Condition True, 0 = Condition False
Running
Bit 1
Forward
Bit 2
Accelerating
Bit 3
Decelerating
Bit 4
b007 [Fault 1 Code]
Related Parameter(s):
,
-
A code that represents a drive fault. [Fault 1 Code] is the most recent fault. Repetitive faults will only
be recorded once.
Refer to
Values
Default:
Read Only
Min/Max:
0/122
Display:
1
b008 [Process Display]
Related Parameter(s):
,
32 bit parameter.
The output frequency scaled by
[Process Factor].
Values
Default:
Read Only
Min/Max:
0.00/9999.99
Display:
0.01 – 1
32
Output
Freq
Process
Factor
Process
Display
=
x
b010 [Output Power]
Output power present at T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0.0/999.9
Display:
0.1 kW